70
PGM activation by users
1.422 - Access report by user
PGM deactivation by users
3.422 - Not used
Communication to CS failed
1.354 - Fail to communicate event
Notes:
1.
In case of CID format was set by programming, then the control panel will transmit to CS the specific reporting codes
regarding “PGM activation/deactivation by users” which are set in this section; after the 4-digit group specific to these
reporting events the panel will transmit to CS another 3-digit group which stands for the user number identifying. In CID
format the “installer’s maintenance code” is identifying as user “000” and PC is identifying as user “255”.
2.
In case in section [29] the alternate reporting was selected and if even after the 8 attempts for both CS phone numbers no
central station answers, then the control panel will record a “CS1 and CS2 communication failed” event into the 400-event
LOG and a specific reporting code into the CS 80-event internal buffer, too. Upon a new reportable event occurring, if the
communication with CS is established, the entire list from CS internal buffer, the old reporting codes, the new reporting
codes and the failed communication reporting code, which is already in the list, will be reported together to the CS. For
“CS1 and CS2 communication failed” event, the panel will report to CS the 4-digit group which is established in this section,
specific to the “Communication to CS failed” event, after which the panel will add another 3 digits of [0], to identify at CS
the “CS1 and CS2 communication failed” event as zone “000”.
3.
In case in section [29] the split (or double) reporting was selected, the panel will report the events as follows:
-
Any event selected in section [30] to be reported to CS1 will be sent to the 1
-st
CS phone number, programmed in
section [74]. If the control panel failed to transmit events to CS1 after 8 attempts (1
-st
CS phone number will not
answer either after the 8
-th
call), then the control panel will record a “CS1 communication failed” event into the 400-
event LOG and the specific reporting code into the CS1 80-event internal buffer. In the same time, in case of split (or
double) reporting, if an event of “CS1 communication failed” is occurring in the system, then the specific reporting
code will be recorded into the CS2 80-event internal buffer and will be transmitted to CS2, too. Upon a new reportable
event occurring, if the communication with CS1 is established, the entire list from CS1 internal buffer, the old reporting
codes, the new reporting codes and the failed communication reporting code, which is already in the list, will be
reported together to the CS1. For “CS1 communication failed” event, the panel will report to CS1 the 4-digit group
which is established in this section, specific to the “Communication to CS failed” event, after which the panel will add
another 2 digits of [0] and 1 digit of [1] for zone, to identify at CS1 the “CS1 communication failed” event as zone
“001”.
-
Any event selected in section [31] to be reported to CS2 will be sent to the 2
-nd
CS phone number, programmed in
section [75]. If the control panel failed to transmit events to CS2 after 8 attempts (2
-nd
CS phone number will not
answer either after the 8
-th
call), then the control panel will record a “CS2 communication failed” event into the 400-
event LOG and the specific reporting code into the CS2 80-event internal buffer. In the same time, in case of split (or
double) reporting, if an event of “CS1 communication failed” is occurring in the system, then the specific reporting
code will be recorded into the CS1 80-event internal buffer and will be transmitted to CS1, too. Upon a new reportable
event occurring, if the communication with CS2 is established, the entire list from CS2 internal buffer, the old reporting
codes, the new reporting codes and the failed communication reporting code, which is already in the list, will be
reported together to the CS2. For “CS2 communication failed” event, the panel will report to CS2 the 4-digit group
which is established in this section, specific to the “Communication to CS failed” event, after which the panel will add
another 2 digits of [0] and 1 digit of [2] for zone, to identify at CS2 the “CS2 communication failed” event as zone
“002”.
S
ECTION
[74]
-
P
HONE
N
UMBER OF
CS1
If the digital communicator is enabled by programming, this is the phone number that the control panel
will dial first to transmit to the “central station” the events occurred in the system.
Enter the phone number in the same way it would be dialed on a touch-tone phone. The maximum
number of digits is 15.
To confirm the phone number, press [#] key after the last digit of the phone number was entered.
After [#] key pressing, the keypad buzzer will sound 6 confirmation beeps and the panel exits the
section and will wait for a new command to enter another section or [#] key to exit the “main
programming menu”.
A 2-second pause can be added by entering HEX digit D between the digits of the phone number (enter
HEX digit D by pressing [*] and [3] keys).
In order to erase the phone number, press [*] key, once the panel entered this section.
Example:
You may want to introduce the phone number 6802054. The following sequence will be entered:
|6||8||0||2||0||5||4||#|. After [#] key pressing, the keypad buzzer will sound 6 confirmation beeps and the panel exits the
section and will wait for a new command to enter another section.
Notes:
1.
In case the
reporting to CS is programmed in [29] section as alternate
, for control panel to initiate CS reporting,
at
least one CS phone number must be programmed in [74] or [75] sections.
If 1
-st
CS phone number is programmed
in this section, this is the phone number that the control panel will dial for the first time in order to transmit to the “central
station” the events occurred in the system.
2.
In case the
reporting to CS is programmed in [29] section as split
(or double), for control panel to initiate CS1
reporting,
this phone number must be programmed in this section.
Please note that if this phone number isn’t
programmed, the control panel will not initiate reporting to CS1 and will not record events into the CS1 80-event internal
buffer anymore, even there in section [30] are events selected to be reported to CS1.