39

ATTRIBUTES

2

 set: 

 ON  OFF 

Remarks 

Zone 4 LED 

Intellizone 

Zone responds as 

normal 

When a zone has the “intellizone” attribute enabled, any first “violation” of 

the zone will start the “timer for intellizones” and then it will 

only

 cause an 

alarm when: 

a)

 

The zone remains violated for the duration of “time window for 
intellizones”. 

b)

 

The zone is violated twice within “time window for intellizones”. 

c)

 

If any 2 “intellizones” are violated within “time window for 
intellizones”. 

Zone 5 LED 

Sensor under 

test 

Zone responds as 

normal

 

When a zone has the “sensor under test” attribute enabled, it will no longer 

trigger the alarm, but each opening/closing of the zone loop will record a 
special event into the 400-event LOG. Each opening of any under test zone 
will record in the specially alarm memory, too, which is keypad displayable 
in section [94], if these zones was violated in the system since the last 
resetting of the especially alarm memory, performed by installer. 

If these zones allow auto shutdown, then during the same arming period 

(or during the same Disarming period for 24h zones), then “swinger 
shutdown
” will be counting the restoration numbers of this zone which was 

violated. In case the number of restorations gets the “swinger shutdown 
counter” value, the respective zone will be automatic “bypassed from 
swinger”. Only this event will be transmitted to the central station. 

Zone 6 LED 

2EOL – with 

zone tamper 

recognition 

EOL – no zone 

tamper recognition

 

When a zone has the “tamper recognition” attribute enabled, short circuit 

or open zone loop are treated as zone tamper condition. Sensors have to 

be connected using the double end-of-line resistor diagram (see page 13). 
In case 

option 2

 in programming 

section 20

 is 

enabled

, no matter if the 

system

 is 

armed or disarmed

, zone tamper condition will activate the 

siren, and the panel will report and save in the event log the tamper alarm 
condition. If this 

option

 is 

disabled

, and the 

system is disarmed

, no 

alarm will be generated in case of zone tamper condition. 

 
After the ATTRIBUTES

2

 set for the selected zone was established to the required values,

 press [#] 

key to confirm.

 

After [#] key was pressed

,

 the keypad buzzer will sound 3 confirmation beeps and the panel will 

pass to the next step, displaying the

 ATTRIBUTES

3

 set 

on 1 and 2 zone LEDs. 

 

While the system is being within 

ATTRIBUTES

3

 displaying submenu, the keypad LEDs’ status will 

be as follows: 

ARMED A LED 

ON 

SYSTEM LED 

Blinking 

READY LED 

ON 

1 and 2 zone LEDs 

ON/OFF

, according to the 

ATTRIBUTES

3

 set 

of the selected zone

 

 
By 

[#] key pressing, ATTRIBUTES

3

 set

 can be maintained

 as it was previously established.

 

 

1.3 

Third set of zone attributes are display-able on 1 and 2 zone LEDs, according to the table below. 

In order to establish the ATTRIBUTES

3

 set

, you should 

press the numeric keys which 

correspond

 to the zone LEDs.

 

After each key pressing the appropriate zone LED switches ON/OFF; if 

the a zone LED is ON that means the appropriate attribute is enabled and if the zone LED is OFF that 
means the attribute is disabled.

 

 

ATTRIBUTES

3

 set: 

 ON 

OFF 

Remarks 

Zone 1 LED 

activate

 

deactivate

 

Zone assigned to partition A 

Zone 2 LED 

activate

 

deactivate

 

Zone assigned to partition B 

 

Содержание Cerber C62

Страница 1: ...Cerber C62 6 Zone and 2 Partition Burglary Control Panel For your home and office Hook Up Programming Book Doc 10401 08 08 2005 version 1 9...

Страница 2: ...n Alarm 18 Zone bypassing 19 System Trouble Status Displaying 4 comand 20 Alarm Memory Displaying 5 21 A different display method for the alarm memory available only for KP 064EP keypads 22 Chime Feat...

Страница 3: ...d protection using micro switch tamper Individual zone LEDs from 1 to 6 indicating the alarm and faulted status Each zone accepts tamper recognition by zone attribute programming and 2EOL wiring Syste...

Страница 4: ...one bypassing automatic from swinger or by the panel during home arming periods if the zones have the attribute stay and manually by the users Programmable zone restore the zone restore event is recor...

Страница 5: ...idually programmable exit and entry delay times for each partition allowed by programming Programmable alarm type silent or audible and for the audible alarms steady or pulsing Individual siren timers...

Страница 6: ...ed by programming Options of arming by users away arming stay arming and instant stay arming allowed by user rights Autoarming options timed autoarming and inactivity autoarming allowed by programming...

Страница 7: ...onic shutdown at 2 2A automatic restore Note Current capability and protections for the auxiliary power supply AUX and for the bell control output BELL as well are valid only if the control panel is p...

Страница 8: ...N in case there is in the system at least one zone bypassed by user and or if there is at least one interior zone bypassed by the system Alternating 3 seconds ON 3 seconds blinking in case both condit...

Страница 9: ...during armed state of the system zone LEDs are ON for 2 seconds and blinking for the next 2 seconds and so on b While the system is completely disarmed or partial armed OFF the loop of corresponding...

Страница 10: ...et Introduce all the system cables into the cabinet through one of the holes especially made for this purpose on the upper and lower parts of the box Prepare the cables for connections MOUNTING THE KE...

Страница 11: ...which require power from a 13 8Vcc supply source The maximum load on these terminals cannot exceed 2A Pay attention to polarity YEL GRN Keypad communication connectors PGM1 PGM2 PGM1 open collector ou...

Страница 12: ...values may be performed only if the appropriate option is enabled by programming see the reset to default lockout option which is displayable on zone 6 LED within 20 section This option assures protec...

Страница 13: ...o many wrong codes which is displayable on zone 1 LED within 20 section in case the successive attempts of entering wrong access codes gets the value set within section 44 the keypad will lock for 7 m...

Страница 14: ...ut the code hasn t the right of force arming all zones must be closed when the system is armed by such a user code After entering a valid user code all keypad LEDs will be ON for a little while and th...

Страница 15: ...he 24 hour clock i e 8 00PM 20 00 as described in 85 and 86 sections INACTIVITY AUTOARMING If inactivity autoarming option is enabled within 26 and or 27 sections and the control panel does not detect...

Страница 16: ...t least one alarm or trouble occurs in the system then the SYSTEM LED will start to blink Because the alarm memory is cleared only upon another system partition arming then after at least one alarm oc...

Страница 17: ...by the users the yellow SYSTEM LED will turn OFF only when Disarming Blinking in case there are troubles in the system AC power loss low voltage on battery fail to communicate event BELL trouble phone...

Страница 18: ...keypad buzzer will sound a long beep Note Quick arming features are allowed only if the appropriate options are enabled by programming see the options displayable on zone 1 2 and 3 LEDs within progra...

Страница 19: ...the user wants to arm the system after the siren sound was stopped he must key in again the user code In a partitioned system entering a user code with the right of siren stopping while siren is sound...

Страница 20: ...is burnt or the fuse near the transformer is burnt this trouble indicator is ON and it will turn OFF once the AC power restored Zone 3 LED Fail to communicate event This trouble indicator will be ON w...

Страница 21: ...needs to be solved before arming to assure a proper function for the system 3 If there are alarms in the memory the SYSTEM LED will turn blinking too if the SYSTEM LED is blinking just because of at...

Страница 22: ...s triggered by zones LEDs of zones that triggered the alarm will also fast blink Press key to view the special alarms triggered from the keypad READY and SYSTEM LEDs will fast blink indicating the sys...

Страница 23: ...d of PGM activation period will change the PGM status from activated to deactivated and vice versa depending if the respective PGM activation period was previously started or stopped The PGM1 or PGM2...

Страница 24: ...he system and zone status 5 Master User s Programming Menus While the system is partially armed in order to enter the main programming menu allowed only to the master user enter one of the 7 Master Co...

Страница 25: ...o 45 user codes the master user should select the corresponding submenu from 01 to 45 by pressing the 2 digit order number of the user code to be programmed erased i e while the system is being within...

Страница 26: ...for the selected user code and the control panel will go back within master user s programming menu Note Do not press key while entering the digits of the selected user code The keypad buzzer will so...

Страница 27: ...ps and the control panel will go back within master user s programming menu after pressing key was enter Notes 1 The master code has all the rights enabled by default and they are programmable only by...

Страница 28: ...r loss events to report these events and the system status too by voice messages or by synthesis sounds specific to these events 5 Up to 4 follow me phone numbers can be programmed by the master user...

Страница 29: ...ster Code 51 Phone number 1 Program the 2 nd Follow me Phone Number 7 Master Code 52 Phone number 2 or CODE Master Code 52 Phone number 2 Program the 3 rd Follow me Phone Number 7 Master Code 53 Phone...

Страница 30: ...ents the day D D month Mo Mo year Y Y hour H H minutes Mi Mi and seconds S S 2 1Once the first 2 digit group corresponding the day D D was entered the keypad buzzer will sound 3 beeps and the zone 2 L...

Страница 31: ...STER USER Some of programming sections which are dedicated to the installer are accessible to the master user too In order to access these programming sections you should use 8 Master Code command whi...

Страница 32: ...m of PC must be already on the phone line and call the control panel While PC modem is calling the control panel just entering this command will manually activate the communication between PC and pane...

Страница 33: ...se the keypad panic alarm should be set of the silence type you should see section 21 System OPTIONS2 zone 6 LED 6 Programming of the System Parameters main programming menu In order to enter the prog...

Страница 34: ...or several programming submenus Once any programming section was selected the system finds itself within 1 st submenu of the programming section which may be a single one and within submenus the syst...

Страница 35: ...t group for the type of the selected zone and ATTRIBUTES1 ATTRIBUTES2 and ATTRIBUTES3 are 1 2 and 3 attribute sets for the selected zone While the system is being within main programming menu you shou...

Страница 36: ...e this zone type is activated the system will be armed disarmed as regards to its previous armed disarmed status If this zone type is violated more than 4 seconds then it will generate a panic alarm t...

Страница 37: ...lsing and for a same zone the set value of this attribute does mater only if the previous attribute was set as audible type The alarm triggered by a zone with this attribute set as steady siren type w...

Страница 38: ...s and the panel will pass to the next step displaying the ATTRIBUTES2 set on zone 1 to 5 LEDs While the system is being within ATTRIBUTES2 displaying submenu the keypad LEDs status will be as follows...

Страница 39: ...attribute enabled short circuit or open zone loop are treated as zone tamper condition Sensors have to be connected using the double end of line resistor diagram see page 13 In case option 2 in progr...

Страница 40: ...d ATTRIBUTE2 sets That means once the 2 digit group standing for some zone type was entered if one try to put respective attribute in the disabled status is pressing the corresponding key to turn OFF...

Страница 41: ...ame as for zone 1 SECTION 05 ZONE 5 DEFINING Do the same as for zone 1 SECTION 06 ZONE 6 DEFINING Do the same as for zone 1 SECTION 20 SYSTEM OPTIONS1 While the system is being within main programming...

Страница 42: ...lect section 22 to establish the system OPTIONS3 Zone LEDs will turn ON OFF according to the table bellow System OPTIONS3 zone LEDs ON OFF Zone 1 LED Activation time for PGM1 as pulse will be in minut...

Страница 43: ...during exit delay Zone 5 LED enabled disabled Warning dings during the 3 minutes before timed autoarming 1ding at every 2 seconds during the warning time before autoarming Zone 6 LED enabled disabled...

Страница 44: ...nabled in this section then the partition A automatically switches to stay arming mode after any regular arming by user by PC or by keyswitch if the user doesn t leave the protected area through any e...

Страница 45: ...t reported to the central stations d Once the phone line trouble TLT is recorded this trouble condition will be displayed on zone 6 LED within system trouble displaying menu 4 command and the keypads...

Страница 46: ...first time then the keypad trouble buzzer warnings will be activated too and the keypad will emit intermittent beeps at every 8 seconds until the users will acknowledge the trouble by means of 4 comm...

Страница 47: ...waiting for handshake pause of 32 seconds and so on up to 8 times for 2 nd CS phone number 4 Within zone restore denomination there is an event which is referring to the recording moment into the 400...

Страница 48: ...o confirm The keypad buzzer will sound 6 confirmation beeps and the panel exits the section waiting for a new command to enter another section or key to exit the main programming menu Notes 1 The opti...

Страница 49: ...are marked with Presses 1 to 4 keys in order to turn the appropriate options activate deactivate The corresponding LEDs will turn ON OFF After setting these options press key to confirm The keypad bu...

Страница 50: ...mming Code Changing 2 in order to program installer s programming code enter the following sequence from the keypad x x x x for 4 digit codes or x x x x x x for 6 digit codes where x x x x and x x x x...

Страница 51: ...ing and the control panel is waiting for the corresponding digit for the new value of the maintenance code 1 PROGRAMMING ERASING OF THE MAINTENANCE CODE MAY BE SKIPPED BY KEY PRESSING 1 1 After key pr...

Страница 52: ...ed disabled Force arming zone 5 LED enabled disabled Disarming siren stopping zone 6 LED reserved reserved Note Installer can disarm the system partition using the maintenance code only if previously...

Страница 53: ...ming ambush by user defined in 63 64 65 and 68 sections 4 As a conclusion the installer s maintenance code will be identified at the central stations as user 0 So these messages from central stations...

Страница 54: ...TS1 displaying session the keypad LEDs status will be as follows ARMED A LED ON SYSTEM LED Blinking READY LED ON 1 to 5 zone LEDs ON OFF according to the RIGHTS1 set for master code the master s right...

Страница 55: ...isn t allowed If by mistake installer is trying to erase the master code by entering of key instead of sequence of 4 or 6 digits while the control panel just entered section 36 the keypad buzzer will...

Страница 56: ...s the keypad buzzer will sound 3 beeps and after key the keypad buzzer will sound 6 confirmation beeps and the panel exits the section waiting for a new command to enter another section To exit the ma...

Страница 57: ...the time lapse after which the control panel starts the voice sound transmitting of the event If meanwhile the AC power is restored the event reporting code and the voice message too are no longer tra...

Страница 58: ...f entering wrong access codes gets the value set in this section the keypad will lock for 7 minutes and all the keypad LEDs will fast blink The event will be memorized into the 400 event LOG which can...

Страница 59: ...OF 20 SECONDS The system will transmit For any ALARM voice message no 1 47 and 48 sections key and zone LED no 1 For AC POWER LOSS voice message no 2 47 and 48 sections key and zone LED no 2 and Synth...

Страница 60: ...e time 01 to 99 seconds of the voice reporting or of the synthesis sounds The following sequence will be introduced __ __ __ __ 02 30 by default 02 voice sound dialing sequences 30 sec The keypad buzz...

Страница 61: ...inking for 3 rd voice message playback c 4 Key and zone 4 LED blinking for 4 th voice message playback 4 If all 1 to 6 zone LEDs are ON that means the voice module MPV8 is configured for 8 voice messa...

Страница 62: ...rder to start 1 st voice message recording you should press 1 key while 1 to 4 zone LEDs are ON then zone 1 LED will start to blink Please note that while recording of any message is performed both LE...

Страница 63: ...panel account The following sequence will be introduced x x x x 0 0 0 0 by default The keypad buzzer will sound 3 beeps after any digit entering and 6 beeps after entering of the last one Then the pan...

Страница 64: ...hich is set in this section irrespective of way the alternate or split reporting option was set 3 The panel will report in the 2 nd reporting format which is set in this section only if the split or d...

Страница 65: ...buzzer will sound 3 beeps after each digit group and 6 beeps after the last digit Then the panel exits the section and will wait for a new command to enter another section To exit the main programming...

Страница 66: ...9 user code 6 key command for round OK round failed and ambush on round events the panel will report to CS the same specific reporting codes established in this section indifferently of zone number z...

Страница 67: ...PROGRAMMED Enter 5 groups of 2 digits HEX digits may be used one group for each reporting event The following sequence will be introduced __ __ __ __ __ __ __ __ __ __ E7 E8 00 00 00 by default The ke...

Страница 68: ...PORTING CODES IN CONTACT ID FORMAT Notes 1 In case of transmission to CS was set in section 51 to be done in CID format 4 account digits 4 event digits 2 partition digits 3 zone user digits after the...

Страница 69: ...o CS another 3 digit group which stands for the zone number identifying SECTION 68 EVENT REPORTING CODES IN CID FORMAT REGARDING Burglary alarm 1 130 Burglary alarm Tamper alarm 1 144 Sensor tamper Pa...

Страница 70: ...o CS2 will be sent to the 2 nd CS phone number programmed in section 75 If the control panel failed to transmit events to CS2 after 8 attempts 2 nd CS phone number will not answer either after the 8 t...

Страница 71: ...stem this is the phone number that the control panel will dial for the second time in case 1 st CS phone number doesn t answer In case the split or double reporting is selected in section 29 then the...

Страница 72: ...ON status to ground once any panic alarm is triggered by a violation of panic zone or by simultaneously pressing of and keys and it will turn OFF only when the siren sound is stopped or only when at...

Страница 73: ...onds for each PGM1 and PGM2 43 courtesy light Once the entry delay time will start this PGM type will turn ON the light and after Disarming this PGM output will remain activated until the time establi...

Страница 74: ...s the section waiting for a new command to enter another section To exit the main programming menu press key SECTION 80 ACTIVATION TIME FOR PGM1 AS PULSE ACTIVATION TIME FOR PGM2 AS PULSE 001 TO 255 S...

Страница 75: ...CLOCK TIMER HOUR MINUTE Enter 2 groups of 2 digits the first 2 digits for the hour 00 to 23 and the second 2 digits for the minute 00 to 59 in this way will be set the daily moment when the PGM2 defin...

Страница 76: ...ne Then the panel exits the section and will wait for a new command to enter another section To exit the main programming menu press key SECTION 88 MOMENT FOR FINISHING THE ROUNDS HOUR MINUTE Enter 2...

Страница 77: ...key Note These 2 passwords from 91 and 92 sections will remain 4 digit codes irrespective of the option setting in section 20 on zone 4 LED SECTION 93 PC PHONE NUMBER FOR CALLBACK This is the PC phon...

Страница 78: ...nd 3 beeps and the zone 3 LED is blinking That means the control panel is waiting for the third 2 digit group corresponding the year Y Y 2 1Once the third 2 digit group corresponding the year Y Y was...

Страница 79: ...section the modem of PC must be already on the phone line and call the control panel While PC modem is calling the control panel just entering section 98 will manually activate the communication betw...

Страница 80: ...ding on the nature of the fire and or the location of the smoke detectors the detector even if operating as anticipated may not provide sufficient warning to allow all occupants to escape in time to p...

Страница 81: ...3 3kOhm 2EOL Resistors 2 2kOhm and 1kOhm Programmable outputs PGM1 and PGM2 2 Maximum load for PGM1 and PGM2 outputs 50mA Main board typical consumption 50mA LED keypad typical consumption 12mA Maxim...

Страница 82: ...82 ROEL electronics S A Calimachi Street 27 29 023496 Bucharest ROMANIA Tel 4 021 204 47 00 Fax 4 021 242 20 30 email sales roel ro www roel ro...

Отзывы: