Installation
Mounting
The controller is convection cooled. Additionally, units rated for 97A
and above are fan cooled. It is important to locate the controller in a
position that allows air to flow vertically through the power module.
The controller must be mounted with heatsink fins in a vertical
plane and have a minimum of six inches (15 cm) free space above
and below the controller.
Dimensions
Figure 2.1 Dimensions: 24, 35, and 54 Amp Controllers
All dimensions are approximate and are not intended for manufacturing purposes. Refer to the nearest Allen-Bradley sales office for complete dimension drawings.
Unit
A
Width
B
Height
C
Depth
D
E
F
G
H
J
Approx.
Ship. Wt.
24A
Controller
mm
154
180
185
50
140
160
140
10
20
4.5 kg
in.
6-1/16
7-3/32
7-19/64
1-31/32
5-33/64
6-5/16
5-33/64
13/32
51/64
10 lbs.
35A
Controller
mm
214
240
195
60
200
200
180
20
30
6.8 kg
in.
8-7/16
9-39/64
7-11/16
2-23/64
7-7/8
7-7/8
7-3/32
51/64
1-3/16
15 lbs.
54A
Controller
mm
244
290
225
90
230
240
200
25
45
11.3 kg
in.
9-39/64
11-22/64
8-7/8
3-35/64
9-1/64
9-29/64
7-7/8
63/64
1-25/32
25 lbs.
Ø .22 in.
(5.56 mm)
4 Mtg. Holes
Ø .28 in.
(7.14 mm)
4 Mtg. Holes
A
E
G F B
D
C
Ground Screw
(10-32)
Содержание SMC Dialog Plus
Страница 46: ...2 20 Installation ...
Страница 78: ...4 14 Programming ...
Страница 149: ...9 6 Diagnostics ...
Страница 157: ...10 8 Troubleshooting Figure 10 3 Removal of Control Module 180 360A 1 3 2 4 ...
Страница 169: ...A 6 Specifications ...
Страница 179: ...C 4 Renewal Parts ...