8-2
Serial Communications
Control Enable
Per factory programming, “stop” is the only control command active
on the SMC Dialog Plus controller when the SCANport is utilized.
To enable motor control from a programmable logic controller
through a communication module, follow the programming procedure
below.
①
Zero and 4 are the only valid settings.
Note:
If a communication module is disconnected from the SMC
Dialog Plus controller while control is enabled (Logic Mask
= 4), a Comm Fault will occur.
Description
Action
Display
—
—
1.
Press any key to access
the Choose Mode
function.
2.
Scroll with the Up/Down
keys until the Program
option appears.
3.
Press the Enter key to
access the Program
option.
4.
Scroll with the Up/Down
keys to the Linear List
option.
5.
Press the Enter key to
access the Linear List
programming group.
6.
Scroll with the Up/Down
keys to parameter number
85 - Logic Mask.
7.
Press the Select key to
move the cursor to the
second line to modify the
parameter.
8.
Press the Up key until the
value 4 appears.
①
9.
Press the Enter key to
accept the new setting.
STOPPED
0.0 AMPS
CHOOSE MODE
_ _ _ _ _
or
CHOOSE MODE
PROGRAM
PROGRAM
_ _ _ _ _
or
PROGRAM
LINEAR LIST
VOLTS PHASE A–B
0 VOLTS
1
or
LOGIC MASK
0
85
LOGIC MASK
0
85
LOGIC MASK
4
85
LOGIC MASK
4
85
Содержание SMC Dialog Plus
Страница 46: ...2 20 Installation ...
Страница 78: ...4 14 Programming ...
Страница 149: ...9 6 Diagnostics ...
Страница 157: ...10 8 Troubleshooting Figure 10 3 Removal of Control Module 180 360A 1 3 2 4 ...
Страница 169: ...A 6 Specifications ...
Страница 179: ...C 4 Renewal Parts ...