Specifications
Electrical Ratings
UL/CSA/NEMA
IEC
Power Circuit
Method of Connection
Motor in delta or star, SCRs between windings and supply
Number of Poles
Equipment designed for three phase loads only
Rated Operation Voltage (Ue)
200–480 VAC (–15%, +10%)
200–600 VAC (–15%, +10%)
200–415VY (–15%, +10%)
200–500VY (–15%, +10%)
Rated Insulation Voltage (Ui)
N/A
500V~
Rated Impulse Voltage (Uimp)
N/A
4000V
Dielectric Withstand
2200 VAC
2500V~
Repetitive Peak Inverse Voltage Rating
200–480 VAC: 1400V
200–600 VAC: 1600V
200–415~: 1400V
200–500V~: 1600V
Operating Frequency
50/60 Hz
50/60 Hz
Utilization Category
MG 1
AC-53a
Protection Against Electrical Shock
N/A
IP 00 (open device)
DV/DT Protection
RC Snubber Network
Transient Protection
Metal Oxide Varistors: 220 Joules @ 24–360A
220 Joules @ 480V, 500–1000A
300 Joules @ 480V, 500–1000A
Short Circuit Protectio
n
SCPD Performance
Type 1
SCPD List
Maximum Fuse or Circuit Breaker
Device Operational
Current Rating (Ie)
Fault Current
Withstand Rating
(A rms sym)
24A
5000
80A
35A
5000
125A
54A
5000
200A
97A
10,000
350A
135A
10,000
500A
180A
10,000
600A
240A
18,000
700A
360A
18,000
1000A
500A
30,000
1200A
650A
30,000
1600A
720A
42,000
2000A
850A
42,000
2500A
1000A
85,000