8-8
Serial Communications
Remote I/O Examples (cont.)
SMC Dialog Plus Controller Logic Control Addresses
①
SMC Dialog Plus Controller Status Addresses
①
SMC Dialog Plus Controller Feedback Address
①
①
The addresses shown are example-specific. Addresses for any given installation can be determined,
based upon the 1203-GD1 communication module switch settings for: rack address, starting group
number, block transfer, logic command/status, and reference/feedback by applying the I/O
addressing format for SLC-500 controllers.
②
The 1747-SN scanner resides in slot 1.
③
Based on the 1203-GD1 communication module switch settings (rack 2, starting group 0). Refer to
the 1747-SN User Manual, Publication 1747-6.6.
④
Refer to Table 8.A.
⑤
Refer to Table 8.B.
Bit Description
I or O
Slot
②
Word
③
Bit
④
Address
Stop
O
1
16
00
O:1.16/00
Start
O
1
16
01
O:1.16/01
Option Command
O
1
16
02
O:1.16/02
Clear Fault
O
1
16
03
O:1.16/03
Bit Description
I or O
Slot
②
Word
③
Bit
⑤
Address
Enabled
I
1
16
00
I:1.16/00
Running
I
1
16
01
I:1.16/01
Starting
I
1
16
04
I:1.16/04
Stopping
I
1
16
05
I:1.16/05
Fault
I
1
16
07
I:1.16/07
At Speed
I
1
16
08
I:1.16/08
I or O
Slot
②
Word
③
Address
I
1
17
I:1.17
Содержание SMC Dialog Plus
Страница 46: ...2 20 Installation ...
Страница 78: ...4 14 Programming ...
Страница 149: ...9 6 Diagnostics ...
Страница 157: ...10 8 Troubleshooting Figure 10 3 Removal of Control Module 180 360A 1 3 2 4 ...
Страница 169: ...A 6 Specifications ...
Страница 179: ...C 4 Renewal Parts ...