Parameter Information
B-3
Table B.1 (cont.) Parameter List
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum
Maximum
Default
Setting
User
Setting
Basic Setup
(cont.)
Slow Speed with Braking
Slow Speed
Select
44
—
—
Low, High
High
Slow Accel
Current
46
% FLC
1
0
450
0
Slow
Running
Current
47
% FLC
1
0
450
0
Braking
Current
48
% FLC
1
0
400
0
Advanced
Setup
Dual Ramp
29
—
—
No, Yes
No
Ramp Time
#2
32
Seconds
1
0
30
10
Initial Torque
#2
33
% LRT
1
0
90
70
Undervolt
Level
52
% Line
Voltage
1
0
99
0 (Off)
Undervolt
Delay
53
Seconds
1
0
99
0
Overvolt
Level
54
% Line
Voltage
1
0
199
0 (Off)
Overvolt
Delay
55
Seconds
1
0
99
0
Jam Level
56
% FLC
1
0
999
0 (Off)
Jam Delay
57
Seconds
10
0.0
10.0
0
Unbalance
Level
58
%
1
0
25
0 (Off)
Unbalance
Delay
86
Seconds
1
0
99
0
Rebalance
59
—
—
Off, On
Off
Underload
Level
60
% FLC
1
0
99
0 (Off)
Underload
Delay
61
Seconds
1
0
99
0
Phase
Reversal
62
—
—
Off, On
Off
Starts per
Hour
63
—
—1
0
99
0 (Off)
Restart
Attempts
64
—
1
0
5
2
Restart Delay
65
Seconds
1
0
60
0
ETM Reset
15
—
—
Off, On
Off
Parameter
Management
17
—
—
Ready, Default Init.
Recll Frm EE,Store In EE
Ready