Programming
4-11
Basic Setup
The Basic Setup programming group provides a limited parameter
set, allowing quick start-up with minimal adjustment. If the user is
planning to implement some of the advanced features (i.e., Dual
Ramp, Phase Rebalance, etc.), then the Advanced Setup
programming group should be selected. It provides all the Basic
Setup parameter set plus the advanced set.
①
Starting Mode must be programmed to Soft Start to obtain access to the Initial Torque parameter.
②
Starting Mode must be programmed to Current Limit to obtain access to the Current Limit Level
parameter.
③
The new programmed parameter values will not be stored to the EEPROM without the user’s
direction in Parameter Management: Store In EE.
Parameter
Option
SMC Option
Displays the type of controller. This is factory set and not
adjustable.
Standard
Starting Mode
Allows the user to program the SMC Dialog Plus
controller for the type of starting that best fits the
application.
Soft Start, Current Limit
Ramp Time #1
This sets the time period during which the controller will
ramp the output voltage.
0 to 30 seconds
Initial Torque #1
①
The initial reduced voltage output level for the voltage
ramp is established and adjusted with this parameter.
0 to 90% of locked rotor
torque
Current Limit Level
②
This parameter provides adjustability for the reduced
output voltage level provided to the motor.
50 to 600% full load
current
Kickstart Time
A boost of 550% of full load current is provided to the
motor for the programmed time period.
0.0 to 2.0 seconds
Stall Delay
Allows the user to program the stall protection delay
time. The delay time begins after the start time has
timed out.
0.0 to 10.0 seconds
Energy Saver
The Energy Saver feature monitors the motor load,
phasing back the voltage output to the motor when the
motor is lightly loaded or unloaded.
Off, On
Aux Contacts 1&2
Form C contacts are provided as standard with the SMC
Dialog Plus controller. These contacts are located at
terminals 18, 19 and 20. Aux Contacts 1&2 allows the
user to configure the operation of the contacts.
Normal, Up-to-speed
Aux Contact 3
A third auxiliary contact is provided between terminals
29 and 30. Aux Contact 3 allows the user to program
the operation of the contact.
Normal, Fault
Contact 3 Config
This parameter provides the user with the ability to
program the “powered up” state of the third auxiliary
contact.
N.O., N.C.
Parameter Mgmt
③
The newly programmed parameters’ values can be
saved to memory, or the factory default parameter
values can be recalled.
Ready, Default Init., Recll
Frm EE, Store In EE