Serial Communications
8-33
Note:
There is no required value for the words identified as “Data
Place Holder”.
Example Ladder Logic Program:
Rung 0: The 1747-SDN scanner module will map output data from its scanner output table (MO) and discrete outputs to each node only when it’s in the
“run mode.” This is accomplished by setting bit 0 of the 1747-SDN’s command word (word 0).
Rung 1: When the START command is initiated at the RSView station the SLC processor sets the output bit mapped to the SMC Dialog Plus controller’s
logic control word start bit. The branch provides a logic “latched” circuit which exerts the START command until input from the SMC Dialog Plus
controller’s status word indicates that it has received the command and has responded appropriately. The SMC Dialog Plus controller will start if no
STOP command is being issued by the SLC or any other control device.
Rung 2: When the STOP command is initiated at the RSView station, the SLC processor sets the output bit mapped to the SMC Dialog Plus controller’s
logic control word stop bit. The branch provides a logic “latched” circuit which exerts the STOP command until input from the SMC Dialog Plus
controller’s status word indicates that it has received the command and has responded appropriately.
1747-SDN
Enable
Bit
SMC
START
Command
SMC
STOP
Command
SMC
START
Command
SMC
STOP
Command
SMC
Running
Bit
SMC
Running
Bit
Start CMD
From
RSVIEW
Stop CMD
From
RSVIEW
: 1
: 1.7
: 1.7
0
1
0
: 1.7
: 1.7
1
0
1
1
: 1.7
: 1.7
B3
B3
272
Содержание SMC Dialog Plus
Страница 46: ...2 20 Installation ...
Страница 78: ...4 14 Programming ...
Страница 149: ...9 6 Diagnostics ...
Страница 157: ...10 8 Troubleshooting Figure 10 3 Removal of Control Module 180 360A 1 3 2 4 ...
Страница 169: ...A 6 Specifications ...
Страница 179: ...C 4 Renewal Parts ...