Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
67
Access Procedures
Chapter 3
Configuring a Pulse Transformer Board FIR3-xx Rev. “L” and Lower
1.
Cut and remove the appropriate sizing resistor(s) (if necessary) from the
pulse transformer board based on the drive AC input voltage, armature
output current, and HP rating shown in
in the
Sizing Resistors Configuration section below.
Sizing Resistors Configuration
The tables below indicate the value of the designated resistor (R1…R5) when left
in place on the pulse transformer board, or indicate “Remove” when the resistor
should be cut off and removed from the board. “–” indicates that this resistor is
not contained on the pulse transformer board for the designated drive size.
Table 12 - 230V AC Input Drives
Table 13 - 460V AC Input Drives
IMPORTANT
This procedure requires a multimeter that measures resistance to thousandths
of an ohm.
Drive Current
Rating Code
DC
Amps
AC Line
Amps
HP
R1
R2
R3
R4
R5
521
521
426
150
–
Remove
5.36
5.36
5.36
Drive Current
Rating Code
DC
Amps
AC Line
Amps
HP
R1
R2
R3
R4
R5
495
495
404.4
300
–
Remove
5.36
5.36
5.36
667
667
544.9
400
–
5.36
5.36
5.36
5.36
=
Sizing resistors are located in the center
of the pulse transformer circuit board.