Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
21
Component Test Procedures
Chapter 2
•
If the voltage measurements above are correct but the value of
parameter 466 [AC Line Voltage] is incorrect, replace the control
board.
5.
Remove the ribbon cable connected to XR on the control board and pulse
transformer board and test the continuity of the cable using the
measurements in
.
If the measurements on the XR cable are correct, replace the pulse
transformer board.
Troubleshoot an Armature
Bridge Failure
If the drive is running unstable or faults with an Overcurrent Fault (F13) an
armature bridge failure may have occurred. All of the signals going to and coming
from the SCR bridges are transmitted via the ribbon cable connected to XR on
the control board and can be measured at these points. See
for location of the XR connector on the control board.
1.
General Safety Precautions on page 10
.
2.
Remove the protective covers from the drive. See
Removal and Installation on page 43
3.
If using a DC output contactor, disconnect the cable from XR on the
control board and measure the signal for each SCR gate as indicated in the
table below:
IMPORTANT
These checks cannot be completed with an AC contactor in use.
Signal Name
XR Cable Pin
Gate
Note
MP
MN
IT1
27
G1
G04
IT2
29
G2
G05
IT3
31
G3
G06
IT4
21
G4 G01
IT5
23
G5
G02
IT6
25
G6
G03
MN
33
–
–
Negative bridge MN - active when high (+5V)
MP
34
–
–
Positive bridge MP - active when high (+5V)