Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
115
Access Procedures
Chapter 3
Install the Bimetal Thermostats
Install the bimetal thermostats in reverse order of removal.
•
Apply thermal grease to the bottom of the bimetal thermostats before
securing them to the heatsink.
•
Use the following table to determine the proper tightening torque for the
screws that secure the SCR modules to the heatsink:
•
Use the following table to determine the proper tightening torque for the
bolts that secure the bus bars to the SCR modules:
Cooling Fans Removal and
Installation
Remove the Cooling Fans
1.
General Safety Precautions on page 10
.
2.
Remove power from the drive. See
Remove Power from the Drive on
.
3.
Remove the covers from the drive. See
Remove the Protective Covers from
4.
Move the control EMI shield. See
Move the Control EMI Shield on
.
ATTENTION:
Thermal grease must be applied to the bottom of the bimetal
thermostats before securing them to the heatsink or damage to the drive may
occur.
230V AC Input
Drive Current
Rating Code
DC Amps
AC Line Amps
HP
Final Torque
521
521
426
150
6 N
•
m (53 lb
•
in)
460V AC Input
Drive Current
Rating Code
DC Amps
AC Line Amps
HP
Final Torque
495
495
404.4
300
4.5…5.5 N
•
m (40…48.7 lb
•
in)
667
667
544.9
400
6 N
•
m (53 lb
•
in)
230V AC Input
Drive Current
Rating Code
DC Amps
AC Line Amps
HP
Final Torque
521
521
426
150
11…13 N
•
m (97.4…115 lb
•
in)
460V AC Input
Drive Current
Rating Code
DC Amps
AC Line Amps
HP
Final Torque
495
495
404.4
300
11…13 N
•
m (97.4…115 lb
•
in)
667
667
544.9
400