Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
99
Access Procedures
Chapter 3
12.
Remove the bolts and washers that secure the horizontal bus bars to the
SCR modules and remove the bus bars.
Continue with Remove the SCR Modules below.
Remove the SCR Modules
1.
Remove the remaining bolts, washers, and metal plates (for regenerative
drives only) from the tops of the SCR modules. Note the order of the
washers on the bolts.
Remove bolts and washers and bus bars
Remove bolts and metal plates
Note
: Regenerative drive shown.
Bolt (32 mm long)
Lock washer
Flat washer
SCR Module
IMPORTANT
Mark all connections and wires before removal to avoid incorrect
wiring during reassembly.