EM-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
18 of 71
Step 6.3.2 Couplin
g
and Tube Assembly (Continued)
Step 6.4 Turbulator Installation
Model
Tube Len
g
th
Minimum
EM-80
20' (6 m)
EM-115
30' (9 m)
EM-150
40' (12 m)
EM-200
50' (15 m)
10' ± 1'
(305 cm ± 25 cm)
Total Overall
Tube Length
7' 6" ± 1'
(229 cm ± 25 cm)
Tw
ist
Pull String
Tab
Fold tab around outside
of tube nearest to the vent to
hold turbulator in place.
Turbulator
Section
Turbulator
Adapter
Description
Part Number
T
u
rb
u
lator Adapter
03051503
T
u
rb
u
lator Section
03051504
T
u
be
91409XXX
Turbulator Installation
EM-80
2nd 10' Section
EM-115
3rd 10' Section
EM-150
4th 10' Section
EM-200
N/A
T
u
rb
u
lator m
u
st be installed in
the last standard section of
t
u
be. T
u
rb
u
lator is not req
u
ired
on the EM-200.