CORAYVAC
®
I
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
42 of 54
2. Ens
u
re that all dampers are in the f
u
lly open
position.
3. T
u
rn off the electrical s
u
pply to the heaters.
4. S
w
itch on the electrical s
u
pply at the main iso-
lator. This
w
ill start the exha
u
st fan.
5. Ens
u
re that all time clocks and thermostats are
set to call for heat.
6.
Balancin
g
Cold Suction
Starting at the branch f
u
rthest from the p
u
mp,
check the end
v
ent
v
ac
uu
m. Do this by con-
necting a manometer by inserting the test
probe a minim
u
m of 150 mm into the hole.
See
Page 49, Figure 31
. Adj
u
st the damper at the
end of the radiant r
u
n so that the s
u
ction is
approximately 9 mbar. Repeat for each branch.
7. S
w
itch off the electrical s
u
pply at the main iso-
lator. The exha
u
st fan
w
ill stop.
8. T
u
rn on the electrical s
u
pply to the heater.
9. S
w
itch on the electrical s
u
pply at the main iso-
lator.
10.
Balancin
g
Hot Suction
The start
u
p seq
u
ence described
on Page 41,
Section 12.1
sho
u
ld take place. Allo
w
the sys-
tem to reach f
u
ll temperat
u
re (approximately 30
min
u
tes). Set the dampers at each branch to
achie
v
e the settings for the installed b
u
rner
model as listed in
12.3.1
.
12.3.1 Suction Settin
g
s
Model
Heat Input
Hot Suction
all Gas Types
(mbar)
CRT10
10 kW
5.7
CRT15
15 kW
6.5
CRT20
20 kW
7.0
CRT25
25 kW
6.7
CRT30
30 kW
7.0
Repeat this proced
u
re for each branch of the
system.
12.4 System Checks
T
u
rn the system off and restart it to ens
u
re smooth
ignition. Carry o
u
t the follo
w
ing system checks.
1. When r
u
nning, t
u
rn off the gas s
u
pply at the
appliance isolating cock. The heater
w
ill imme-
diately sh
u
t do
w
n follo
w
ed by 3 attempts at res-
toration follo
w
ed by locko
u
t.
2. When r
u
nning, disconnect the fan electrical
s
u
pply. The b
u
rner sho
u
ld sh
u
t do
w
n
w
ithin a
fe
w
seconds pro
v
ing operation of the press
u
re
s
w
itch.
3. When r
u
nning, t
u
rn do
w
n the thermostat to a
point belo
w
room temperat
u
re. Check that the
fan contin
u
es to r
u
n on for t
w
o min
u
tes after
sh
u
t do
w
n of the b
u
rners.
12.5 User Instructions
After satisfactory testing, ens
u
re that the client is
f
u
lly a
w
are of the operation of the system. Bring this
man
u
al to the attention of the
u
ser or p
u
rchaser;
instr
u
ct them in the safe operation of the heater(s).
12.6 ECA Approved Systems
On ECA appro
v
ed systems, it m
u
st be
v
erified that
the req
u
irement of 91% net comb
u
stion efficiency is
met. Meas
u
rements of temperat
u
re and CO
2
con-
centration in the exha
u
st gasses ha
v
e to be done.
The net comb
u
stion efficiency calc
u
lates as follo
w
s;
100 - [ (t
E
- t
R
) (A/CO
2m
- B) ] = net comb. efficiency
t
E
- Exha
u
st Temperat
u
re °C
t
R
- Room Temperat
u
re °C
A
- G20 = 0.37, G31 = 0.42
B
- G20 = 0.009, G31 = 0.008
CO
2m
-Meas
u
red CO
2
Concentration %