: GENERAL VENTING REQUIREMENTS FOR PUMPS
8
.1 Ventin
g
Re
q
uirements
All
v
enting m
u
st conform
w
ith national and local
codes.
Any portion of
v
ent pipe passing thro
u
gh a
comb
u
stible
w
all m
u
st ha
v
e an appro
v
ed thimble
to conform
w
ith national and local codes.
Vent pipe m
u
st be sloped do
w
n
w
ard a
w
ay from the
p
u
mp 6 mm e
v
ery 3048 mm.
The bottom of the
v
ent or air intake terminal shall not
be located less than 304 mm abo
v
e grade le
v
el.
The
v
ent shall not terminate less than 2100 mm
abo
v
e grade
w
here located adjacent to p
u
blic
w
alk
w
ays.
Vent terminal m
u
st be installed at a height s
u
fficient
to pre
v
ent blockage by sno
w
, and b
u
ilding materials
protected from degradation by fl
u
e gases.
Sec
u
re all joints
w
ith #8 x 3/8 sheet metal scre
w
s.
Seal all joints
w
ith high temperat
u
re silicone sealant.
Vent terminal m
u
st be beyond any comb
u
stible
o
v
erhang.
8
.1.1 Vertical Ventin
g
See Page 33, Figure 20
for recommended
v
ertical
v
enting options.
8
.1.2 Horizontal Ventin
g
See Page 32, Figure 19
for recommended horizontal
v
enting options.
WARNING
Carbon Monoxide Hazard
Multiburner systems are not approved for
unvented use and must be vented outdoors.
Heaters must be installed according to the
installation manual.
Failure to follow these instructions can result
in death or injury.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.