CORAYVAC
®
I
NSTALLATION
O
PERATION
AND
S
ERVICE
M
ANUAL
34 of 54
an electrical j
u
nction box on its side. Press
u
re s
w
itch
control
w
ires and electrical po
w
er connection need
to be connected here. A
w
iring diagram is inside the
j
u
nction box.
See Figure 22
.
The mo
u
nting of the enclos
u
re m
u
st be done as
described in
Section 8.2 on Page 29
.
Figure 22:
Acoustic Enclosure
Figure 23:
Junction Box Wirin
g
Dia
g
rams
8
.6.1 Noise Data
All noise data has been determined according to E
N
ISO 3746:1995, s
u
r
v
ey method "Parallelepiped
meas
u
rement s
u
rface". Val
u
es gi
v
en belo
w
are at 3 m distance from the object.
Tailpipe
Connection
Flue
Discharge
Junction Box
(wiring diagram
inside)
F
rom
Pressure
Switch
F
rom
F
an
Motor
Blue
Brown Brown
Blue
Black
Earth
Common NO
U
1
V
1
W1
3 Ø Motors
F
rom
Pressure
Switch
F
rom
F
an
Motor
Blue
Brown
Brown
Blue
Earth
Common NO
1 Ø Motors
RG30 and RG45 Pump Data
Sound Pressure Level
dB (A)
NR
No acoustic enclosure
59
53
No acoustic enclosure with 600 mm silencer
59
53
With acoustic enclosure
57
51
With acoustic enclosure and 600 mm silencer
55
49
Flue Data
Straight outlet duct
69
63
Straight outlet duct with 600 mm silencer
60
54
Burner Data
CRT 10 - 30 located at end vent plate
58
52
CRT 10 - 30 located in middle of branch
49
43