6 ERRORS
Manual ERZ2000-DI · EN1.2 · 2017, December 21st
115
250
R
95-0
Math.problem
Mathematical error
1
Yes
No
251
A
95-1
Corrupt code
corrupt code detected
1
No
No
252
A
95-2
Alarm volume
hard-wired contact of volume transmitter shows alarm
2
No
No
253
W
95-4
Time sync fail
Time synchronization failed
1
No
No
254
H
95-5
Net time error
Net time error
1
No
No
255
R
95-6
HART9 failure
HART 9 input failed
2
No
No
256
R
95-7
HART10 failure
HART 10 input failed
2
No
No
257
A
96-7
Hs GC timeout
No more signal from the superior calorific value transmitter
2
Yes
No
258
A
96-8
sd GC timeout
No more signal from standard density transmitter
2
Yes
No
259
A
97-0
CO2 GC timeout
No more signal from CO2 transmitter
2
Yes
No
260
H
97-3
Hs GC alarm
GC reports loss of superior calorific value
2
Yes
No
261
H
97-4
sd GC alarm
GC reports loss of standard density
2
Yes
No
262
H
97-6
CO2 GC alarm
GC reports loss of carbon dioxide
2
Yes
No
263
W
98-4
CH4<l.warn.lim.
Methane below lower warning limit
2
Yes
Yes
264
W
98-5
CH4>up.warn.lim.
Methane exceeds upper warning limit
2
Yes
Yes
265
A
98-7
Comp.normaliz.
Error occurred during normalization of gas components
2
Yes
Yes
266
A
98-8
Inval.act.key
Invalid activation key
2
No
No
267
H
99-4
Adjusted float
Floating point parameter adjusted to floating-point notation
1
No
No
268
A
99-7
AGA8 alarm
AGA 8 algorithmic error
2
Yes
Yes
269
A
99-8
AGA892DC alarm
AGA 8 92DC algorithmic error
2
Yes
Yes
270
W
88-2
Signature error
Problems with signature
1
No
No
271
H
57-1
Qu param.
Parameter inconsistent flow
2
No
No
272
W
57-2
Memory RAM
less RAM
2
No
No
273
W
57-3
Memory SDCard
less memory on SD-Card
2
No
No
274
H
57-5
MAC ETH2
Reboot required, Eth2 MAC has changed
2
No
No
275
M
57-6
Custody commis.
custody commissioning triggered
2
No
No
276
A
57-7
CRC WinCE
WinCE-Kernel wrong CRC
2
No
No
277
A
57-8
Param.Attack
Parameter file was attacked
1
No
No
278
W
57-9
FilesysWarn
noncritical WinCE file system error
1
No
No
279
A
58-8
FilesysAlarm
critical WinCE file system error
1
No
No
280
H
58-9
Service mode
Service mode is active
1
No
No
281
H
40-3
C6 conflict
Serial interface C6 protocol in conflict
2
No
No
282
H
40-4
C7 conflict
Serial interface C7 protocol in conflict
2
No
No
283
A
10-0
Pulse cmp. 1:1
Pulse comparision error 1:1
1
Yes
Yes
284
A
10-1
Pulse cmp. X:Y
Pulse comparision error X:Y
1
Yes
Yes
285
A
99-0
GERG2008 alarm
GERG2008 algorithmic error
1
Yes
Yes
286
A
99-1
GERG2004 alarm
GERG2004 algorithmic error
1
Yes
Yes
287
A
99-2
AGA8(2017) alarm
AGA8(2017) algorithmic error
1
Yes
Yes
288
A
99-3
GOST 30319 alarm GOST 30319 algorithmic error
1
Yes
Yes
Содержание ERZ2000-DI Series
Страница 6: ......
Страница 81: ...3 ELECTRICAL CONNECTIONS Manual ERZ2000 DI EN1 2 2017 December 21st 75 Figure 61 Rear wall of the ERZ2000 DI ...
Страница 99: ...4 TRANSMITTERS Manual ERZ2000 DI EN1 2 2017 December 21st 93 Figure 69 Measuring path arrangement USM GT400 ...
Страница 142: ...Certificates Manual ERZ2000 DI EN1 2 2017 December 21st 136 ...
Страница 143: ...Certificates Manual ERZ2000 DI EN1 2 2017 December 21st 137 ...