The values of the 2 meters can be set in the coordinates
LG02 Vb1
to
LG30 DE2
.
A negative value means that this meter is not set. The coordinate
LP99 Task
defines
the various assignments that can be viewed in the table below.
Idle
Nothing happens!
All TOT = 0
All totalizers (main+disturbance) and fractions are set to 0.
The totalizers are also set to 0 for undefined billing mode.
All DTOT = 0
All disturbance totalizers and fractions are set to 0. The
totalizers are also set to 0 for undefined billing mode. The
main totalizers remain unaffected
Vm = Vo
All Vm totalizers (uncorrected operating volume) are set to
the current value of the assigned Vo totalizer (original total-
izer). All other totalizers remain unaffected.
Vc = Vm
All Vc totalizers (corrected operating volume) are set to the
current value of the assigned Vm totalizer (uncorrected op-
erating volume). All other totalizers remain unaffected.
Custom
All totalizers that were programmed with a non-negative
value in the totalizer settings list are set to this value. In this
connection, the portion after the decimal is written to the
fraction totalizer. Then the relevant input field in the settings
list is set to -1. All totalizers that are negative in the totalizer
settings list (explicitly -1) remain unaffected.
All overflow = 0
All overflows are set to 0.
Содержание ERZ2000-DI Series
Страница 6: ......
Страница 81: ...3 ELECTRICAL CONNECTIONS Manual ERZ2000 DI EN1 2 2017 December 21st 75 Figure 61 Rear wall of the ERZ2000 DI ...
Страница 99: ...4 TRANSMITTERS Manual ERZ2000 DI EN1 2 2017 December 21st 93 Figure 69 Measuring path arrangement USM GT400 ...
Страница 142: ...Certificates Manual ERZ2000 DI EN1 2 2017 December 21st 136 ...
Страница 143: ...Certificates Manual ERZ2000 DI EN1 2 2017 December 21st 137 ...
Страница 144: ...Certificates Manual ERZ2000 DI EN1 2 2017 December 21st 138 ...