13 Further technical information
EN
44
Rittal Liquid Cooling Package
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
37
T air [K]
12
12
12
12
12
12
Cooling output, sensible [kW]
20
20
20
20
20
20
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
22
22
22
22
23
23
Water volume [l/min]
30
34
36
40
44
50
Volumetric airflow [m
3
/h]
4000
4000
4000
4000
4000
4000
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
40
40
40
40
40
40
T air [K]
15
15
15
15
15
15
Tab. 52: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
18
18
18
18
18
18
Tab. 51: Cooling output at full load and a
T air of 12 K