13 Further technical information
EN
36
Rittal Liquid Cooling Package
20 kW devices 3311.600/700/800/900
Volumetric airflow [m
3
/h]
2400
2500
2500
2500
2500
Air outlet from LCP Hybrid [°C]
22
22
22
22
22
Air inlet to LCP Hybrid [°C]
34
34
34
34
34
T air [K]
12
12
12
12
12
Cooling output, sensible [kW]
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
18
18.5
19
19
19
Water volume [l/min]
24
28
30
37
45
Volumetric airflow [m
3
/h]
2000
2100
2100
2100
2100
Air outlet from LCP Hybrid [°C]
22
22
22
22
22
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
T air [K]
15
15
15
15
15
Tab. 24: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
10
10
10
10
10
Tab. 23: Cooling output at full load and a
T air of 12 K
Cooling output, sensible [kW]
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
19
19
20
20
20
20.5
Water volume [l/min]
32
36
38
40
48
60
Volumetric airflow [m
3
/h]
3600
3600
3600
3600
3600
3600
Air outlet from LCP Hybrid [°C]
22
22
22
22
22
22
Air inlet to LCP Hybrid [°C]
34
34
34
34
34
34
T air [K]
12
12
12
12
12
12
Tab. 25: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
20
20
20
21
21
21
Water volume [l/min]
28
32
36
38
46
54
Volumetric airflow [m
3
/h]
3100
3100
3100
3100
3100
3100
Air outlet from LCP Hybrid [°C]
22
22
22
22
22
22
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
37
T air [K]
15
15
15
15
15
15
Tab. 26: Cooling output at partial load and a
T air of 15 K