13 Further technical information
EN
42
Rittal Liquid Cooling Package
13.2.8 Cooling output at a room temperature of
25°C
10 kW devices 3311.610/710/810/910
Air inlet to LCP Hybrid [°C]
39
39
39
39
39
39
T air [K]
15
15
15
15
15
15
Cooling output, sensible [kW]
20
20
20
20
20
20
Tab. 44: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
26
25
24
24
23
23
23
Water volume [l/min]
5
6
7
8
10
12
14
Volumetric airflow [m
3
/h]
1200
1200
1200
1300
1300
1300
1300
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
37
37
T air [K]
12
12
12
12
12
12
12
Tab. 45: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
26
25
25
25
24
24.5
23.5
Water volume [l/min]
5
6
7
8
10
12
14
Volumetric airflow [m
3
/h]
1000
1000
1000
1100
1100
1100
1100
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
40
40
40
40
40
40
40
T air [K]
15
15
15
15
15
15
15
Tab. 46: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
10
10
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
20
20
21
21
21.5
22
22
Water volume [l/min]
18
20
22
24
26
30
34
Volumetric airflow [m
3
/h]
2400
2500
2500
2500
2500
2500
2500
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
37
37
T air [K]
12
12
12
12
12
12
12
Tab. 47: Cooling output at full load and a
T air of 12 K