Rittal Liquid Cooling Package
33
13 Further technical information
EN
13.2.4 Cooling output at a room temperature of
21°C
10 kW devices 3311.610/710/810/910
Cooling output, sensible [kW]
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
19
19
19
19
19.5
19.5
20
Water volume [l/min]
10
11
14
19
21
28
40
Volumetric airflow [m
3
/h]
1200
1200
1200
1300
1300
1300
1300
Air outlet from LCP Hybrid [°C]
21
21
21
21
21
21
21
Air inlet to LCP Hybrid [°C]
33
33
33
33
33
33
33
T air [K]
12
12
12
12
12
12
12
Tab. 13: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
19
19.5
19
19
19.5
20
20
Water volume [l/min]
10
11
14
19
21
28
40
Volumetric airflow [m
3
/h]
1000
1000
1000
1100
1100
1100
1100
Air outlet from LCP Hybrid [°C]
21
21
21
21
21
21
21
Air inlet to LCP Hybrid [°C]
36
36
36
36
36
36
36
T air [K]
15
15
15
15
15
15
15
Tab. 14: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
17.5
17.5
18
18
18
Water volume [l/min]
26
30
30
46
58
Volumetric airflow [m
3
/h]
2400
2500
2500
2600
2400
Air outlet from LCP Hybrid [°C]
21
21
21
21
21
Air inlet to LCP Hybrid [°C]
33
33
33
33
33
T air [K]
12
12
12
12
12
Tab. 15: Cooling output at full load and a
T air of 12 K
Cooling output, sensible [kW]
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
17.5
18
18
18
19
Water volume [l/min]
26
30
35
46
58
Volumetric airflow [m
3
/h]
2000
2100
2100
2100
2100
Tab. 16: Cooling output at full load and a
T air of 15 K