5 Assembly and siting
EN
5
Assembly and siting
5.1
General
5.1.1
Installation site requirements
In order to ensure problem-free operation of the Liquid
Cooling Package, the following conditions for the instal-
lation location should be observed:
Supply connections required at the installation site
Tab. 2:
Supply connections required at the installation site
Floor conditions
– The floor of the installation space should be rigid and
level.
– Choose the installation site so that the unit is not situ-
ated on a step or uneven surface, etc.
5.1.2
Installation guidelines
The positioning in the rack aisles must be considered
when planning the layout. In particular, care should be
taken to ensure that external air streams are not pointing
directly at the rear of the LCP Hybrid. Such counterflows
prevent hot air from being expelled by the LCP Hybrid,
leading to the formation of a hot spot inside the server
enclosure.
Fig. 10:
Incorrect external air stream
Key
1
Cold ambient air
2
Server rack with installed equipment
3
Hot spot caused by failure to expel hot air
4
LCP Hybrid with air/water heat exchanger
5
External air stream onto the LCP Hybrid
A serial layout is the best option. This means that cold air
produced by the LCP Hybrid is drawn in by a server en-
closure positioned behind it. The LCP Hybrid installed
there cools the air from this enclosure, and so on.
If several server enclosures are positioned adjacent to
one another, each enclosure must be partitioned sepa-
rately. To this end, we recommend using a partition be-
tween two enclosures, and a corresponding side panel
as the termination.
Type of connection
Connection description:
Cooling water con-
nection:
15°C inlet temperature (depend-
ing on relative humidity)
Max. 6 bar permissible operating
pressure
Volumetric flow: depending on
design (see section 13.2 "Charac-
teristic curves and tables")
DN 25 (G1") external pipe thread
Note:
Please also observe the instructions and data
relating to the cold water connection as out-
lined in section 6.1 "Cooling water connec-
tion".
Recommendation:
To facilitate easy servicing of the Liquid
Cooling Package, maintain a distance of at
least 1 m between the rear of the device and
the nearest wall.
Recommendation:
Room tempe22°C at 47% relative air
humidity, according to ASHRAE guidelines.
The room temperature must correspond to
the required air intake temperature.
Caution! Risk of tipping over!
Stand-alone enclosures should be se-
cured to the floor to prevent them tip-
ping over.