5 Assembly and siting
EN
16
Rittal Liquid Cooling Package
Fig. 16:
Mounting the LCP Hybrid – Inside top
Key
1
Server enclosure
2
Assembly screws (2x)
3
LCP Hybrid
Secure the LCP Hybrid at the inside bottom using two
screws included with the supply.
Fig. 17:
Mounting the LCP Hybrid – Inside bottom
Key
1
LCP Hybrid
2
Position for potential equalisation
3
Assembly screws (2x)
4
Server enclosure
5.2.6
Fitting the potential equalisation
In order to ensure reliable potential equalisation between
the server enclosure and the LCP Hybrid, it is addition-
ally necessary to fit the special potential equalisation
screw.
Screw the potential equalisation screw and contact
washer included with the supply into the point marked
with an earth symbol above the bottom two assembly
screws, as far as they will go (fig. 17, item 2).
5.2.7
Install the air routing kit (optional)
It is also important to ensure correct routing of the heat-
ed air through the LCP Hybrid for the devices installed at
the top and bottom of the server enclosure. To this end,
the air routing kit (3311.160) available as an accessory
should be mounted at the rear on the inside of the server
enclosure frame.
First, insert one air baffle plate each from above into
the corresponding fastening plate.
Fig. 18:
Air routing kit at the bottom of the server enclosure
Key
1
Assembly screw, air baffle plate – fastening plate (3x)
2
Server enclosure
3
Assembly screw, fastening plate – server enclosure (3x)
4
482.6 mm (19") level
5
Fastening plate
6
Air baffle plate
Secure the air baffle plate in this position using a total
of three assembly screws.
Mount the fastening plate, including the air baffle plate,
at the bottom rear of the server enclosure frame, and
secure it in this position, likewise with three assembly
screws.
Fit the second air baffle plate in the server enclosure as
outlined above.
5.2.8
Remove the mounting aid
Finally, remove the mounting aid beneath the Liquid
Cooling Package.
1
2
2
3
1
2
3
3
4
Note:
The side position of the air baffle plate is de-
termined by the 482.6 mm (19") chassis.
6
4
3
1
2
5