Rittal Liquid Cooling Package
43
13 Further technical information
EN
20 kW devices 3311.600/700/800/900
Cooling output, sensible [kW]
10
10
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
17
16
Return temperature [°C]
20
20.5
21
21
22
22
22
Water volume [l/min]
20
22
24
26
28
32
38
Volumetric airflow [m
3
/h]
2200
2200
2200
2300
2300
2300
2300
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
40
40
40
40
40
40
40
T air [K]
15
15
15
15
15
15
15
Tab. 48: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
21.5
22
22
23
23
23
Water volume [l/min]
23
25
26
28
32
35
Volumetric airflow [m
3
/h]
3700
3700
3700
3700
3700
3700
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
37
37
37
37
37
37
T air [K]
12
12
12
12
12
12
Tab. 49: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
22
22
22.5
23
23
24
Water volume [l/min]
24
26
28
30
32
35
Volumetric airflow [m
3
/h]
3200
3200
3200
3200
3200
3200
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
Air inlet to LCP Hybrid [°C]
40
40
40
40
40
40
T air [K]
15
15
15
15
15
15
Tab. 50: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
18
18
18
18
18
18
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
21
21
22
22
22.5
22
Water volume [l/min]
30
32
34
37
40
50
Volumetric airflow [m
3
/h]
4500
4500
4500
4500
4500
4500
Air outlet from LCP Hybrid [°C]
25
25
25
25
25
25
Tab. 51: Cooling output at full load and a
T air of 12 K