Reference Manual Rev 1.13
004R-646-113
Page 109
17.4.1.
Additional Settings
In addition to the common settings the following settings control the operation of
the OVER and UNDER setpoints
SOURCE
: Select the weight source for the setpoint to use.
Options are:
GROSS uses gross weight only
NET uses net weight only
‘GR or NT’ uses either gross or net depending on which is
currently displayed.
ALT.GR uses alternate gross weight only
ALT.NET uses alternate net weight only
ALT.G or N uses either alternate gross of alternate net
depending on which is currently displayed.
REG uses a register value.
SCOPE
: GLOBAL means that the same targets are used for every
product. PROD lets each product have its on target values for the
setpoint.
Hysteresis (HYS)
: This setting determines the change in weight required
for an active setpoint to become inactive again. A value of zero still
leaves 0.5 graduations of hysteresis.
REG
: If the source is set to register (REG) then this setting is used to set
the register to use. The register must be a number or weight value.
17.5. Status Based Setpoint Types
The following setpoint types are all based on the status of the instrument.
NONE
: Setpoint is always inactive.
ON
: Setpoint is always active. This type of setpoint is useful to show that the
instrument is running.
Centre of Zero (COZ)
: Setpoint is active when COZ annunciator is lit.
ZERO
: Setpoint is active when the weight is within the Zero Band setting.
o
SOURCE: The ZERO setpoint also has a SOURCE setting to
determine if the zero condition is based on the gross or net reading.
The GR.or.NT option uses the currently selected weight (gross or net).
NET
: Setpoint is active when the NET annunciator is lit.
MOTION
: Setpoint is active when the MOTION annunciator is lit.
ERROR
: Setpoint is active when the instrument detects any error condition
signified by the display of Exxxxx on the primary display.
BUZZER
: Setpoint is active when buzzer beeps.
17.6. Logic Setpoint Types
The following setpoint types are all based on the status of the inputs and the mask.
Содержание AxleweighR R420
Страница 45: ...Reference Manual Rev 1 13 004R 646 113 Page 45 8 6 Two Pass 8 7 Two Pass Automatic Temporary ID Allocated...
Страница 48: ...Reference Manual Rev 1 13 Page 48 004R 646 113 9 5 Two Pass 9 6 Two Pass Automatic Temporary ID Allocated...
Страница 51: ...Reference Manual Rev 1 13 004R 646 113 Page 51 10 5 Two Pass 10 6 Two Pass Automatic Temporary ID Allocated...
Страница 85: ...Reference Manual Rev 1 13 004R 646 113 Page 85 13 1 1 ZERO Zero Calibration Routine...