Rinnai
25
ES_FIM
COMPONENT ASSEMBLY & CONNECTION "IN-WALL" FLUE ~ ESFKIT03 & ESKITIW
The In-Wall vertical Co-Axial flue system is installed within a stud wall with cavity depth a minimum of 90mm and
is run vertically upwards through the stud wall cavity and includes a condensate trap.
When considering the location of the heater due care
MUST
be taken to ensure that the flue path in the internal
wall and roof space are free of obstructions such as studs, noggins, joists, braces, and electricals etc. A top plate
bracket is provided to seal the flue penetration through the top plate.
1.
Use the lower end points (
iv
and
vi
) of the flue spigot arc from "Wall Penetrations" on page 10 to determine
the shaded spigot area
ix
.
Point
H
is the centre point of the transition casting and the point from which all measurements are taken. The
starting point
H
may be placed anywhere within the shaded spigot area
ix
.
Using the dimensions shown above create a 300mm high by 200mm wide opening. The bottom left corner of
this opening is 75mm to the left of starting point
H
and 50mm below starting point
H
.
2.
!
Remove the screw from the front of the transition casting (retain and
DO NOT
discard) and slide the wall
spacer plate over the transition casting so that the folded tab is facing both down and to the rear.
Using the screw removed from the front of the transition casting attach the mounting strip across the front of
the transition casting.
Lubricate the O-Ring of the condensate trap and attach this to the transition assembly
!
ensuring that
the drain tube is facing to the front.
3.
Install the above assembly in to the wall cavity
!
observing the measurements shown to ensure the
correct fitting of heater and other components. Secure in place with appropriate fixings.
Outline of mounting strip
Outline of vermin plates
Required wall penetration
Bottom left corner of opening
300mm
200mm
75mm
50mm
i
(Appliance outline example RHFE-556)
iii
(Centre of flue elbow pivot point)
ix
(Spigot area derived from
lower end points
iv
and
vi
)
D
(Minimum limit of arc)
Use in conjuction with section “WALL PENETRATIONS” on page 6.
Align this point within
the shaded area
iv
.
H
1
2
3
Transition Casting/
Condensate Trap
Wall Spacer Plate
Mounting Strip
117
mm
75mm
H
Condensate Drain
Tube Connection
Wall Spacer Plate
(Installed Position)
Pipe Locating Spacer
(See page 19 for deatails)
INSTALLATION METHODS