Installation & Servicing Instructions Rinnai E-Series
66
15.2 Blocks
An error, which has been detected, is indicated on the display by a block message.
Blocks can be temporary in nature. The controller will do everything possible to prevent
a system lock and temporarily switching off the boiler as a result of a block. Please
see below for a summary of blocks.
Blocks
with a
fi
gure on the last 2 characters.
Code
Description
Solution
External safety contact open
Rectify error as a result of which by determining contact is open.
Or repair interconnection between 24/25
Outdoor sensor contact open (not
connected)
Rectify error as a result of which by determining contact is open or
outdoor sensor is not connected.
Connect outdoor sensor or repair wiring (position 18/19) or replace
outdoor sensor.
Maximum average
T of supply and
return sensor for central heating is
repeatedly exceeded. Operation is
normally possible for the hot water
supply during the block. The pump
continues to operate at minimum
capacity during the block.
Check
fl
ow through the installation.
See the installation instructions for the hydraulic connections to the
boiler
(3-Way-Thermostatic valve, Plumbing Kit installed?)
Possible causes: (radiator) shut-off valves closed or blocked water
fi
lter
Activeted room sensor (RS101) in non leading room (closed thermostatic
radiator valves?) Check pump height.
Check minimum and maximum Temperature difference in Parameter Step
46 + 47.
Maximum average
T of supply
and return sensor for hot water is
repeatedly exceeded. Operation
is normally possible for the central
heating installation during the block.
The pump continues to operate at
minimum capacity during the block.
Check
fl
ow through the boiler and DHW tank
See the installation instructions for the hydraulic connections to the boiler
Possible causes: (radiator) shut-off valves closed or blocked water
fi
lter
resistance (coil) in tank to high (see pump height)
Check 3-way-valve on function and pollution.
Incorrect parameter setting for the
minimum or maximum power
Call Rinnai
A temperature difference has been
detected between the supply and
return sensor whilst the burner is
not in operation. After the average
T has disappeared, the block will
disappear.
Check the supply and return sensor for the resistance value and replace
the defective sensor
Check the installation for any external heat source and rectify this
fl
ue sensor temperature too high
Check vent system
fl
ue sensor or thermostat contact
open
Call Rinnai
fl
ue sensor or thermostat contact
closed
Call Rinnai
fl
ue gas thermostat contact open
Check vent system
or check parameter 84 for default
no water
fl
ow can be detected
through the controller. De-aeration
cycle is started. When water
fl
ow
is detected during this cycle, the
de-aeration cycle is terminated
and the burner is released.
The controller checks the water
pressure during static and
dynamic situation.
- check the installation for the presence of air;If there is a secondary
pump installed and it is not hydraulicly separated, it could cause
pressure differences.
- check the use of balancing valves
check if the pump is functioning and/or that the water pressure sensor is
working properly;
Polluted pump;
Polluted water pressure sensor;
Polluted water
fi
lter;
Wiring of pump.
The frequence of the power supply
deviates more than + or -1.5Hz
check the main power supply
Содержание E50C
Страница 43: ...Installation Servicing Instructions Rinnai E Series 43 electrical ladder diagram figure 23a ...
Страница 84: ...Installation Servicing Instructions Rinnai E Series 84 ...
Страница 127: ...Installation Servicing Instructions Rinnai E Series 127 Schéma électrique en échelle figure 23a ...