![Rinnai E50C Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/rinnai/e50c/e50c_installation-and-servicing-instructions-manual_1462446060.webp)
Installation & Servicing Instructions Rinnai E-Series
60
13.3 Maintenance activities
The fan unit and burner cassette (
fi
gure 32 to 34) (every 4 year maintenace)
- Remove the electrical connection plug from the gas valve (1) and fan motor (2);
- Loosen the nut (3) of the gas pipe under the gas valve;
-
Replace the gasket with a new one
;
- Loosen the front cross head screw (4) of the black plastic silencer;
- After this turn the two clamping rods (9 and 10) ¼ turn and remove them by pulling
them forward.
Note the correct turning direction (red indicator. fi g. 34)
;
- Slightly lift the fan unit and remove it towards the front of the heat exchanger;
- Remove the burner cassette out of the fan unit;
- Check the burner cassette for wear, pollution and possible cracks. Clean the
burner cassette with a soft brush and vacuum cleaner.
If burners are cracked replace the complete burner cassette;
-
Replace the gaskets between burner and fan unit and the gasket between
fan unit and heat exchanger
;
- Check the venturi and the gas-air distribution plate for pollution and clean this part,
if necessary with a soft brush and vacuum cleaner. If the air box contains a lot
of dirt it is plausible that the fan itself is dirty as well. To clean this, the fan has to
be removed from the hood and the venturi. Clean the fan with a soft brush and a
vacuum cleaner. Replace the gasket and ensure that all gaskets of the fan parts
are mounted correctly.
Heat exchanger (every 4 year maintenance)
- Check the heat exchanger for contamination. Clean this if necessary with a soft
brush and a vacuum cleaner. Prevent debris from falling down into the heat
exchanger.
Flushing the heat exchanger from the top down is not permitted
Re
fi
tting of the components is done in reverse order.
Make sure that during refi tting the clamping rods they are put in the right
position. They should be turned vertical.
If the boiler should activate with clamping rods in the wrong position it will
cause property damage, personal injury or loss of life.
Ignition electrode (every 4 year maintenance)
This can be checked by measuring the ionization current. The minimum ionization
current has to be higher than 4
μ
A on full load.
If the inspection glass is damaged the complete electrode must be replaced.
Replace the ignition assembly after every 4 year, whichever occurs
fi
rst.
Replacement goes as follows:
- Remove the electrical connections of the electrode;
- Press the clips on both sides of the electrode to both sides and remove the complete
electrode;
- Remove and replace the gasket;
Re
fi
tting of the components is done in reverse order.
fan unit and gas valve
fi gure 32
NOTICE
i
NOTICE
i
NOTICE
i
!
DANGER
figure
33
Clamping rods
figure 34
10
1
2
3
9
4
Содержание E50C
Страница 43: ...Installation Servicing Instructions Rinnai E Series 43 electrical ladder diagram figure 23a ...
Страница 84: ...Installation Servicing Instructions Rinnai E Series 84 ...
Страница 127: ...Installation Servicing Instructions Rinnai E Series 127 Schéma électrique en échelle figure 23a ...