When the recirculation logic starts, the pump will operate as described below.
When the boiler detects the crossover valve is closed, the pump will turn off.
After the off interval timer of the boiler has passed, the pump will turn on again.
A minimum flow rate 0.5 GPM (2 L/min) is needed for the boiler to operate correctly
(maximum current: 2 Amps). Select the proper pump size based on the crossover valve
and DHW system pressure loss.
Note: The maximum current permissible to connect to the DHW_Pump connection is 2 Amps.
Timer Connects to T/T 2 Terminal
DHW Recirculation Pump Connect to
“DHW_Pump Terminal” (label on PC Board)