Rinnai I-Series Condensing Boiler Combi Manual
Curve 4 is a custom curve based on the target setpoint temperature of the boiler the customer
selects. The maximum temperature is the target temperature. The minimum temperature is 36°F
lower than the target temperature with a minimum of 104°F. See example curves below.
Curve 4
To select the desired reset curve, access the parameters (as shown in section “12.4 Parameter
Settings”) and select parameter . Then, select the desired curve.
Parameter
Number
Setting Description
Selection
Outdoor reset curve
1
2
3
4
Select Reset Curve
190°F
(88°C)
180°F
(82°C)
170°F
(77°C)
160°F
(71°C)
150°F
(66°C)
140°F
(60°C)
130°F
(54°C)
120°F
(49°C)
110°F
(43°C)
100°F
(38°C)
(-29°C) (-23°F) (-18°C) (-12°C) (-7°C) (-1°C) (4°C) (10°C) (16°C)
(21°C)
114°F
(46°C)
104°F
(40°C)
-20°F -10°F
0°F 10°F 20°F 30°F 40°F 50°F 60°F 70°F
104°F Minimum
Temperature
170°F
(77°C)
150°F
(66°C)
130°F
(54°C)
14°F
(-10°C)
68°F
(20°C)
134°F
(57°C)