Rinnai I-Series Condensing Boiler Combi Manual
Type of Heat Emitter
Typical Minimum
Supply Temperature
Typical Maximum
Supply Temperature
Hydronic Air Handler
120 - 140°F
140 - 180°F
Unit Heater
130 - 140°F
160 - 180°F
Base Board Convectors
100 - 140°F
140 - 180°F
Cast Iron/Panel Radiator
90 - 120°F
140 - 180°F
Undermount Radiant
100 -120°F
120 - 150°F
Below are some typical target temperatures for various heat emitters. These are basic guidelines; thus,
check with
the emitter manufacturer or consult your heating design engineer.
Note: If temperatures lower than 104°F are necessary, a mixing valve may be needed in the system.
1. Remove the boiler’s front panel by removing the four screws that secure the panel.
2. Locate the PC Board (lower left side of unit).
3. Connect the outdoor sensor to the terminals shown below using minimum 18 AWG wiring to the two
terminals provided in the enclosure.
4. Locate the DIP switches on the PC Board (see below). Ensure that DIP switch 1 is in the OFF (Default)
position (this ensures the boiler will operate based on the outdoor temperature).
5. Set parameters 01 - 03 as appropriate for your application (see Parameter Settings Table for more
information).
Outdoor
Temperature
Sensor
OFF
DIP switch 1 in OFF (Default) position
IMPORTANT
If DIP switch 1 is set to the OFF (default) position, and the wire harness to the
outdoor sensor is disconnected, then error code E393 will display. While the E393
error is displayed, the boiler will operate under the setting temperature control.
PC Board
Содержание COMBI i060C
Страница 124: ...124 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 125: ...Rinnai I Series Condensing Boiler Combi Manual 125 ...
Страница 134: ...134 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 135: ...Rinnai I Series Condensing Boiler Combi Manual 135 ...
Страница 136: ...136 Rinnai I Series Condensing Boiler Combi Manual 800000111 3 2019 ...