48
Rinnai I-Series Condensing Boiler Combi Manual
The gas supply must be capable of handling the entire gas load
required at the location. Gas line sizing is based on gas type,
the pressure drop in the system, the gas pressure supplied,
and gas line type. For gas pipe sizing, refer to the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and
Propane Installation Code, CSA B149.1
For some tables, you will need to determine the cubic feet per
hour of gas required by dividing the gas input by the heating
value of the gas (available from the local gas company). The
gas input needs to include all gas products at the location and
the maximum Btu usage at full load when all gas products are
in use.
Use the table for your gas type and pipe type to find the pipe
size required. The pipe size must be able to provide the
required cubic feet per hour of gas or the required Btu/hr.
The information below is provided as an example. The
appropriate table from the applicable code must be used.
Schedule 40 Metallic Pipe
Inlet Pressure: Less than 2 psi
Specific Gravity: 0.60
Information in table obtained from
NFPA 54, ANSI Z223.1 - 2015.
Pressure Drop 0.5 in. w.c.
Nominal Pipe Size (in.)
1/2
3/4
1
1 1/4
Length in ft (meters)
Capacity in Cubic Feet of Gas per Hour
10 (3)
172
360
678
1,390
20 (6)
118
247
466
957
30 (9)
95
199
374
768
40 (12)
81
170
320
657
50 (15)
72
151
284
583
60 (18)
65
137
257
528
70 (21)
60
126
237
486
80 (24)
56
117
220
452
90 (27)
52
110
207
424
100 (30)
50
104
195
400
EXAMPLE
Rinnai Model Gas Input:
Additional Appliance Total Gas
Input:
Heating Value of Gas:
Cubic Feet Per Hour (CFH):
ANSWER:
B
65,000
Btu/hr
C
1,000
Btu/ft
3
A
199,000
Btu/hr
199,000+65,000
(CFH) =
1000
264
FT
3
/HR
CFH
=
For this example, the pipe
diameter must be at least 3/4 in.
pipe size and 10 ft (3 m) in
length.
A + B
(CFH) =
C
Instructions: Enter values in empty boxes.
Rinnai Model Gas Input:
Additional Appliance Total Gas Input:
Heating Value of Gas:
Cubic Feet Per Hour (CFH):
ANSWER:
B
Btu/hr
C
Btu/ft
3
A
Btu/hr
(CFH) =
FT
3
/HR
CFH
=
A + B
(CFH) =
C
GAS PIPE SIZING CALCULATION WORKSHEET
Natural Gas
Содержание COMBI i060C
Страница 124: ...124 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 125: ...Rinnai I Series Condensing Boiler Combi Manual 125 ...
Страница 134: ...134 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 135: ...Rinnai I Series Condensing Boiler Combi Manual 135 ...
Страница 136: ...136 Rinnai I Series Condensing Boiler Combi Manual 800000111 3 2019 ...