64
Rinnai I-Series Condensing Boiler Combi Manual
Devices such as the room thermostat, outdoor temperature sensor, zones pumps, and relay
controls are connected to the boiler PC Board.
□
Confirm that the electricity is supplied from a 120 VAC, 60 Hz power source and is in a
properly grounded circuit.
□
Confirm that an extension cord or adapter plug has NOT been used with the boiler.
□
Confirm connection terminals are connected correctly.
PC Board
❼
❻
❹
❺
❽
Item #
Connection Item
Note
Internal Pump Connection
120 VAC
External Pump Connection 2
120 VAC, Max 2.0 A
External Pump Connection 1
120 VAC, Max 2.0 A
T/T 1 Connection
T/T 2 Connection
LWCO (High Limit or Other
Safety Switch)
Included Jumper
from Factory
Outdoor Temperature Sensor
24V AC for External Output
Max 0.7 A
❶
❷
❸
❹
❺
❻
❼
❽
❶
❷
❸
Rinnai recommends the use of spade connectors or
similar components for wiring to the screw terminals.
Ensure that the insulation of the wire is not exposed
to contact any other components besides the
terminal.
If exposed wiring contacts to any other exposed
wiring or metal components, an electrical short may
occur and cause damage to the PCB or other
connected components.
Use proper size of screwdriver for preventing the
screw on the terminal from breaking.
Do not use an electric or torque screwdriver for
wiring on the PC Board.
Wiring should pass through the grommets provided
at the bottom of the boiler.
Use proper diameter and size of wiring.
CAUTION
Содержание COMBI i060C
Страница 124: ...124 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 125: ...Rinnai I Series Condensing Boiler Combi Manual 125 ...
Страница 134: ...134 Rinnai I Series Condensing Boiler Combi Manual ...
Страница 135: ...Rinnai I Series Condensing Boiler Combi Manual 135 ...
Страница 136: ...136 Rinnai I Series Condensing Boiler Combi Manual 800000111 3 2019 ...