5-3. How to start the gas detector
Before supplying power (24 VDC) to the detector, check that the detector is installed properly.
Supply power (24 VDC) to the detector (turn on the detector).
After the detector completes the start-up, it enters the detection mode swiftly.
NOTE
<<Start-up Operation Procedures>> (approximately 25 seconds for system check of the detector and alarm
deactivation)
Power on -> Initial clear (approximately 25 seconds) -> Detection mode
WARNING
When the detector enters other mode from the detection mode while an alarm is activated, the alarm
is reset.
CAUTION
Do not turn off the detector during the initial clear. The detector is reading the internal memory
during the initial clear.
If the detector is installed newly or the new sensor is replaced, the sensor must be warmed up
for a specified period which is determined depending on the type of the sensor after the
detector is started.
After the warm-up is completed, perform a span adjustment.
Power On
Detection Mode
Initial Clear