5 How to Operate
5-6. How
to exit
- 26 -
<Setting Display "1-2">
Display various setting values.
5-6. How to exit
To turn off the detector, turn off the power supply (24 VDC) to the detector.
1-2.
Press SET key.
To 1-2
Alarm Setpoint Display
Alarm Delay Time Display
(seconds)
Zero Suppression Value
Display
Alarm Contact Specification
Display
AL.
: The contact is activated due to the
gas alarm.
FAU.
: The contact is activated due to the
fault alarm.
A. or F.
: The contact is activated due to the
gas alarm or the fault alarm.
WARNING
When the detector is turned off, an alarm may be triggered on the upper (central) system.
Before turning off the detector, INHIBIT (point skip) on the upper (central) system must be
activated. Decide whether the power can be turned off by checking the operation of the devices
connected to the external output or external contact output terminal of the detector.
If the alarm contact is energized (option), it is activated when the detector is turned "OFF".