2 Important Notices on Safety
2-4. Safety
Information
- 7 -
<TIIS Specifications>
Technical Data
(Protection Method)
Flameproof enclosure
(Explosion-proof class)
Ex d
II
C T6X
(Ambient Temperature)*
-20
C to +53
C
(Electrical Data)
Supply voltage: DC24V 45mA
Detecting element output signal: DC0.1V 0.2mA
Analog signal output: DC24V 22mA
Contact output (Contact capacity): AC250V 0.5A (Load resistance)
DC30V 0.5A (Load resistance)
(Applicable Standard)
JNIOSH-TR-NO. 43(2008)
*The ambient temperature on explosion-proof certification is described above and it indicates the
temperature range which can maintain the explosion-proof performance and not the product performance,
see
“10-1. List of specifications” for details.
Installation
GND
Sig+
RLY
GND
Sig+
RLY
Indicator etc.
24V
Gas Detector (SD-1OX)
Hazardous Location
(Zone 1)
Nonhazardous Location
Installation Diagram
CVVS Cable
24V
Содержание PT2-177
Страница 1: ...PT2E 1771 Smart Transmitter Gas Detector Head SD 1OX Operating Manual PT2E 177 PT2 177 ...
Страница 3: ......
Страница 56: ......