7 Maintenance
7-2. Regular
maintenance mode
- 36 -
<Gas Test "2-0.0">
<Alarm Test "2-0.1">
2-0.0
Press SET key.
Introduce the test gas and perform the gas
test.
Stop introducing the test gas. When the
reading increases, press the MENU/ESC key
to cancel the test and to go back to the
original state.
To 2-0.0
WARNING
Be careful to perform the test because the contact and gas concentration output can be activated by
a gas test even in the maintenance mode depending on setting.
2-0.1
Press SET key.
Alarm Test ON/OFF
(The contact setting is "Alarm" or "Alarm or
Fault")
Select either ON/OFF, and then press the
SET key.
Perform the gas alarm test by increasing or
decreasing the reading with the
▲ or ▼ key.
Press the MENU/ESC key to cancel the test
and to go back to the original state.
To 2-0.1
WARNING
Be careful to perform the test because the contact and gas concentration output can be activated by
an alarm test even in the maintenance mode depending on setting.