6
TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20
°
C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 8)(A)p.8, with zero pressure in the combustion chambre an maximum burner output.
(2) Sound pressure measured in manufacturerÕs combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional):
¥
KIT FOR LPG OPERATION
: the kit allows the 30 - 40 BLU burners to operate on LPG.
¥
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valve, pressure governor and Þlter):
see page 18.
MODEL
RS 30 BLU
RS 40 BLU
TYPE
831 T1
827 T1
OUTPUT
(1)
2nd stage
kW
210 - 350
181 - 300
325 - 465
280 - 400
Mcal/h
min. 1st stage
kW
130
112
175
150
Mcal/h
FUEL
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
G20
G25
- Net caloriÞc value
kWh/Nm
3
Mcal/Nm
3
10
8,6
8,6
7,4
10
8,6
8,6
7,4
- Absolute density
kg/Nm
3
0,71
0,78
0,71
0,78
- Max delivery
Nm
3
/h
35
40
46
54
- Pressure at maximunm delivery
(2)
mbar
13,3
19,7
13,8
20,4
OPERATION
- Intermittent (min. 1 stop in 24 hours)
- Two - stage (high and low ßame) and single-stage (all - nothing)
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATURE
°
C
0 - 40
COMBUSTION AIR TEMPERATURE
°
C max
60
ELECTRICAL SUPPLY
V
~ 50 Hz 230 V (+/- 10%)
ELECTRIC MOTOR
W
V
A
420
220 - 240
2,9
420
220 - 240
2,9
MOTOR CAPACITOR
m
F / V
12,5/450
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1x 8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
W max
600
ELECTRICAL PROTECTION
IP 44
ELECTROMAGNETIC COMPATIBILITY
90/396 - 89/336 - 73/23 - 92/42
NOISE LEVELS
(3)
dBA
70
70
APPROVAL
CE
0063AR4682
APPROVAL
BUWAL Nr
196020
BURNER
RS 30 BLU
RS 40 BLU
OUTPUT
kW
130
¸
350
175
¸
465
CODE
3010148
3010149
COUNTRY
CATEGORY
IT - AT - GR - DK - FI - SE
II
2H3B / P
ES - GB - IE - PT
II
2H3P
NL
II
2L3B / P
FR
II
2 E r 3 P
DE
II
2ELL3B /P
BE
I
2E(R)B,
I
3P
LU
II
2E3B /P
Important:
The installer is responsible for the addition of any safety device not forseen in the present manual.
GB