Faults - Possible causes - Solutions
127
#
EEPROM access internal error
Carry out a reset, repeat and check the last setting of the
parameters. Restore the group of parameters: if the error arises
repeatedly, replace the control box.
128
0
EEPROM access internal error - synchronisation
during the initialisation
Carry out a reset; If the error arises repeatedly, replace the
control box.
129
#
EEPROM access internal error – command
synchronisation
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
130
#
EEPROM access internal error - time-out
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
131
#
EEPROM access internal error - page interrupted
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
132
#
EEPROM register initialisation internal error
Carry out a reset; if the error arises repeatedly, replace the
control box.
133 ÷ 135
#
EEPROM access internal error – request
synchronisation
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
136
1
Restoration started
The restoration of a backup has been started (no error)
137
#
Internal error – backup / restoration
157 (-99)
Restoration – OK, but backup < compared with set data of
current system
Restoration successful, but the backup data installed are fewer
than those currently present in the system.
239 (-17)
Backup - logging of the backup on RDI21… failed
Perform the reset and repeat backup
240 (-16)
Reset - no backup in RDI21…
No backup in RDI21…
241 (-15)
Reset - Interruptions relating to impracticable ASN
The backup has an impracticable ASN and cannot reset the
unit
242 (-14)
Backup – the backup carried out is contradictory
The backup is irregular and cannot be transferred again
243 (-13)
Backup – the data comparison between the internal
microprocessors is irregular
Repeat the reset and backup
244 (-12)
The backup data are incompatible
The backup data are incompatible with the current version of
the software; the restoration is not possible
245 (-11)
Error in access to the parameter Restore_Complete
Repeat the reset and backup
246 (-10)
Restoration – time-out during logging in EEPROM
Repeat the reset and backup
247 (-9)
The data received are contradictory
The series of backup data is not valid; restoration is not
possible
248 (-8)
The restoration cannot currently be carried out
Repeat the reset and backup
249 (-7)
Restoration – interruption caused by inadequate
identification of the burner
The backup has an inadequate identification of the burner and
must not be transferred to the control box
250 (-6)
Backup – the CRC of a page is not correct
The series of backup data is not valid; restoration is not
possible
251 (-5)
Backup – the identification of the burner is not defined
Define the identification of the burner and repeat the backup
252 (-4)
After restoration, the pages are still in INTERRUPTION
Repeat the reset and backup
253 (-3)
The restoration cannot currently be carried out
Repeat the reset and backup
254 (-2)
Interruption owing to transmission error
Repeat the reset and backup
255 (-1)
Interruption owing to time-out during the restoration
Carry out a reset, check the connections and repeat the backup
146
#
Time-out of the system automation interface
Refer to the Modbus User Documentation (A7541)
1
Modbus time-out
150
#
TÜV test
1 (-1)
Invalid phase
The TÜV test can only be started in phase 60 (operation)
2 (-2)
The TÜV test default output is too low
The output of the TÜV test must be lower than the minor output
limit
3 (-3)
The TÜV test default output is too high
The output of the TÜV test must be greater than the upper
output limit
4 (-4)
Manual interruption
No error: Manual interruption of the TÜV test by the user
5 (-5)
TÜV test time-out
No flame loss after the fuel valves have been closed
1. Check for any extraneous lights
2. Check that there are no short-circuits
3. Check whether one of the valves is leaking
165
#
Internal error
166
0
Watchdog reset internal error
Error
code
Diagnostic code
Meaning of the LMV 26... system
Recommended measures
Содержание RLS 310/E MX
Страница 2: ...Original instructions ...
Страница 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Страница 82: ...20081825 80 GB Appendix Electrical panel layout RLS 310 410 510 610 E MX 400V Star Triangle Start Up ...
Страница 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Страница 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Страница 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Страница 94: ......
Страница 95: ......