Faults - Possible causes - Solutions
12
#
Valve leak detection control
0
V1 leaks
Leak test
Check if the valve on the side of the gas has any leaks.
Check the wiring and make sure that the circuit is open.
1
V2 leaks
Leak test
Check if the valve on the side of the burner has any leaks.
Check if the pressure switch for the leak test (PGVP) is closed
when gas pressure is not present.
Check the wiring and check if there is a short circuit.
2
Valve leak detection test not possible
The valve leak detection is active, but the minimum gas
pressure switch is selected as input for X9-04 (check
parameters 238 and 241)
3
Valve leak detection test not possible
The valve leak detection is active, but no input has been
assigned (check parameters 236 and 237)
4
Valve leak detection not possible
Valve leak detection is active, but 2 inputs have already been
assigned (configure parameter 237 or maximum gas Pressure
switch or POC)
5
Valve leak detection not possible
The valve leak detection is active, but 2 inputs have been
assigned (check parameters 236 and 237)
14
#
POC
0
POC Open
Check if the closure contact of the valve is closed
1
POC Closed
Check the wiring
Check if the closure contact of the valve opens when the valve
is checked
64
POC Open - Alarm lockout at start
Check the wiring
Check if the closure contact of the valve is closed
19
80
Fuel pressure, POC - Alarm lockout at start
Check that the pressure switch is closed when no pressure is
present from the fuel
Check that there are no short-circuits
20
#
Pmin
0
Minimum gas/oil pressure absent
Check that there are no line interruptions
1
Scarcity of gas - Alarm lockout at start
Check that there are no line interruptions
21
#
Pmax/POC
0
Pmax: Max. gas/oil pressure exceeded
POC: POC open (software version
V02.00)
Check the wiring.
POC: check whether the closure contact of the valve is closed
1
POC closed (software version
V02.00)
Check the wiring.
Check if the closure contact of the valve opens when the valve
is checked
64
POC Open - Lockout alarm at the start (software version
V02.00)
Check the wiring.
Check if the contact of the valve opens when the valve is
checked
Error
code
Diagnostic code
Meaning of the LMV 26... system
Recommended measures
Содержание RLS 310/E MX
Страница 2: ...Original instructions ...
Страница 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Страница 82: ...20081825 80 GB Appendix Electrical panel layout RLS 310 410 510 610 E MX 400V Star Triangle Start Up ...
Страница 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Страница 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Страница 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Страница 94: ......
Страница 95: ......