Start-up, calibration and operation of the burner
300
BURNER CHECKS (FUEL 1)
301
Burner operation mode (fuel supply line, modulating/
stage, servomotors, etc.)
-- = not defined (eliminate curves)
1 = Gmod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2 stage
6 = Lo 3 stage
7 = Gmod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod only gas actuator
20 = Gp1 mod only gas actuator
21 = Gp2 mod only gas actuator
22 = Lo mod only oil actuator
1
-
Modify/set to
zero
1
22
1
Not defined
Service Mode
321
(Fuel 1)
Gas: selection of flame sensor
0 = QRB.../ QRC
1 = ION / QRA
1
-
Modification
0
1
1
1
Service Mode
322
(Fuel 1) Gas: Selection of the pre-purging function
0 = deactivated
1 = activated
1
-
Modification
0
1
1
1
Service Mode
323
Maximum repeats of minimum gas pressure switch
intervention
1 = No repetition
2...15 = Number of repetitions
16 = Constant repetitions
1
-
Modification
1
16
1
16
Service Mode
325
(Fuel 1) Gas: pre-purging time
1
s
Modification
20s
60 min
0.2s
20s
Service Mode
326
(Fuel 1) Gas: Spark pre-ignition time
1
s
Modification
0.4 s
60 min
0.2s
2s
Service Mode
330
(Fuel 1) Gas: interval 1
1
s
Modification
0.4 s
60s
0.2s
2s
Service Mode
332
(Fuel 1) Gas: interval 2
1
s
Modification
0.4 s
60s
0.2s
2s
Service Mode
333
(Fuel 1) Gas: post-combustion time
1
s
Modification
0.2s
60s
0.2s
8s
Service Mode
334
(Fuel 1) Gas: Post-purging time (no extraneous light
test)
1
s
Modification
0.2s
108 min
0.2s
0.2s
Service Mode
336
(Fuel 1) Gas: Minimum gas pressure switch input
0 = deactivated
1 = minimum gas pressure switch (upstream of the
fuel valve 1 (V1))
2 = valve control via the minimum pressure switch
(between fuel vale 1 (V1) and 2 (V2))
1
-
Modification
1
2
1
1
Service Mode
337
(Fuel 1) Gas: Maximum gas pressure switch / POC
Input
0 = deactivated
1 = Maximum gas pressure switch
2 = POC
3 = Leak detection control pressure switch
1
-
Modification
1
2
1
1
Service Mode
341
(Fuel 1) Gas: Valve leak detection test
0 = test deactivated
1 = valve leak detection test at start up
2 = valve leak detection test at shutdown
3 = valve leak detection test at start-up and at shut-
down
1
-
Modification
0
3
1
2
Service Mode
348
(Fuel 1) Gas: Post-purging time (t3)(at deactivation of
the load (LR)) - ON
1
s
Modification
1s
108 min
0.2s
1s
Service Mode
361
(Fuel 1) Oil: selection of flame sensor
0 = QRB.../ QRC...
1 = ION / QRA...
1
-
Modification
0
1
1
0
Service Mode
Parameter
No. of
elements
Unit of
measure-
ment
Modifica-
tion
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
Description
Min.
Max.
Содержание RLS 310/E MX
Страница 2: ...Original instructions ...
Страница 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Страница 82: ...20081825 80 GB Appendix Electrical panel layout RLS 310 410 510 610 E MX 400V Star Triangle Start Up ...
Страница 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Страница 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Страница 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Страница 94: ......
Страница 95: ......