45
20081825
GB
Start-up, calibration and operation of the burner
Once the access procedure has been carried out, the display will
show
“PArA”
for a few seconds.
Select the group of parameters with keys
“+”
and
“-”
, and con-
firm by pressing the key
“i/reset”
.
Within the group you have chosen, scroll through the list with the
keys
“+”
and
“-”
. At the end of the list, the display visualises
“End
“.
To return to Normal visualisation mode, simultaneously press the
keys
“+”
and
“-”
(
ESC
) twice.
6.11.4.2 Assigning parameter levels
The parameters level is subdivided into groups as shown on page
45.
Tab. R
To modify a parameter, refer to the
“Parameter modification
procedure”
.
6.12
Parameter modification procedure
After accessing the level and group of parameters, the display
visualises the number of the parameter (flashing) on the left, and
the corresponding value on the right.
If the value is not visualised, press the key
“i/reset”
for 1 - 3
seconds.
Find below an example of how to modify the parameter relating
to the
pre-purging time
(No. 225).
Press the key
“i/reset”
: the value
20
(seconds) will appear.
NOTE:
The unit of measurement of the time is not visualised but is un-
derstood in seconds.
Press the key
“+”
and increase the value to
25
seconds (flash-
ing). Press the key
“i/reset”
to confirm and store.
To return to the list of parameters, press the keys
“+”
and
“-”
(
ESC
) simultaneously.
WARNING
The password must only be communicated to the
qualified personnel or the Technical Assistance
Service, and must be kept in a safe place.
D9022
P
s
h min
%
V
/reset
ESC
No.
Parameter
100: ParA
General parameters
Information and identification data of the system.
200: ParA
Burner checks (Fuel 0)
Type of operation, intervention and safety times
of the various phases.
300: ParA
Burner checks (Fuel 1)
Type of operation, intervention and safety times of
the various phases.
400: Set
Air/fuel modulation curve
Setting of air/fuel adjustment points
500: ParA
Positioning of servomotors
Choice of positions of the air/fuel servomotors in
the various phases.
600: ParA
Servomotors
Setting and addressing of the servomotors.
700: HISt
Log of the errors:
Choice of different visualisation modes for the er-
rors log.
900: dAtA
Process information
Visualisation of information for the remote man-
agement of the burner.
WARNING
All the parameters are checked in the factory.
Modification/tampering may compromise the
good operation of the burner and cause injury to
people or damage to things. In any case, modifi-
cations must be carried out by qualified person-
nel.
D9028
P
%
s
min
h
/reset
D9029
h min s
%
V
P
D9030
P
V
%
s
h mi
/reset
D9031
P
%
s
h min
ESC
Содержание RLS 310/E MX
Страница 2: ...Original instructions ...
Страница 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Страница 82: ...20081825 80 GB Appendix Electrical panel layout RLS 310 410 510 610 E MX 400V Star Triangle Start Up ...
Страница 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Страница 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Страница 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Страница 94: ......
Страница 95: ......