INStAllAtION
Minimum floor area for indoor unit (m²)
Gas charge
Indoor unit installation
kg
floor
Window
Wall
Ceiling
1,10
No requirements
1,224
1,225
12,88
4,64
1,43
0,96
1,30
14,50
5,22
1,61
1,08
1,90
30,98
11,15
3,44
2,30
2,00
34,32
12,36
3,81
2,55
2,30
45,39
16,34
5,04
3,38
2,60
58,00
20,88
6,44
4,31
3,00
77,22
27,80
8,58
5,74
3,50
105,11
37,84
11,68
7,82
A
Minimum floor area
B
Refrigerant charge
C
Floor
D
Window
E
Wall
f
Ceiling
110
A (m²)
82,5
55
27,5
0
1
1,75
3,35
2,5
4
B (kg)
C
D
E
F
Check that:
—
the support wall is able to support the device weight
—
the wall section does not feature building supporting ele-
ments, pipes or power lines
—
the supplied wall plugs are suitable for the chosen support
wall
Avoid:
—
installing the device in hallways or passageways
—
any obstacles or barriers that will cause the expelled air to
recirculate
—
locations with aggressive or explosive atmospheres or with
inflammable fluids
—
direct exposure to sunlight and proximity to heat sources
—
humid locations or positions where the unit could come
into contact with water
—
environment containing oil vapours
—
locations with high frequency contamination
9
Avoid placing the unit less than 1 metre away from radio and
video systems.
2.7
Recommended distances
The distances for the device installation and maintenance are
shown in the figure. The indicated spaces are necessary in order
to prevent the airflow from being blocked, as well as to allow
normal cleaning and maintenance operations to be carried out.