background image

AMW P

3

TAbLE OF CONTENTS

GENERAL INFORMATION

  . . . . . . . . . . . . . . . . . . 

p. 4

1.1 

General Notices  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 4

1.2 

Safety precautions  . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 4

1.3 

Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 5

1.4 

Safety and adjustment devices. . . . . . . . . . . . . . . . . . 

p. 5

1.5 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 5

1.6 Layout  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 5

1.7 

Technical specifications  . . . . . . . . . . . . . . . . . . . . . . . 

p. 6

1.8 

Cooling circuit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 6

2 INSTALLATION

  . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 7

2.1 

Receiving the product  . . . . . . . . . . . . . . . . . . . . . . . . 

p. 7

2.2 

Labels positioning  . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 7

2.3 

Dimensions and weight . . . . . . . . . . . . . . . . . . . . . . . 

p. 7

2.4 Storage  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 8

2.5 

Handling and removal of the packing  . . . . . . . . . . . . 

p. 8

2.6  Place of installation  . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 8

2.7 

Recommended distances. . . . . . . . . . . . . . . . . . . . . . 

p. 9

2.8  Installation on old systems or systems in need of 

upgrading  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 10

2.9 Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 10

2.10  Condensate discharge position  . . . . . . . . . . . . . . . . .

p. 12

2.11  Refrigerating connection  . . . . . . . . . . . . . . . . . . . . . .

p. 12

2.12  Condensate discharge connection  . . . . . . . . . . . . . . .

p. 15

2.13  Wiring diagram  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 16

2.14  Electrical connection  . . . . . . . . . . . . . . . . . . . . . . . . 

p. 16

2.15  Remote control  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

p. 17

2.16  Unit display  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 19

COMMISSIONING AND MAINTENANCE

  . . . . 

p. 20

3.1 

Preparation for first commissioning  . . . . . . . . . . . . . 

p. 20

3.2 

Putting into service  . . . . . . . . . . . . . . . . . . . . . . . . . .

p. 21

3.3 

Temporary shutdown. . . . . . . . . . . . . . . . . . . . . . . . .

p. 21

3.4 

Stop for an extended period of time  . . . . . . . . . . . . .

p. 21

3.5 

Ordinary maintenance . . . . . . . . . . . . . . . . . . . . . . . 

p. 22

3.6  Extraordinary maintenance  . . . . . . . . . . . . . . . . . . . 

p. 23

3.7 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 23

4 DISPOSAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

p. 24

The following symbols are used on the product:

The R32 refrigerant gas is slightly inflammable and 
odourless. Avoid proximity to sources of ignition in 
continuous operation (open flames, gas household 
appliances, electric stoves, lit cigarettes, etc).
For more information, see the installation and tech-
nical service instructions.
before performing maintenance and service tasks, 
read the installation and technical service instruc-
tions.
before the installation, read the installation and 
technical service instructions.

The following symbols are used in this publication:

WARNING = actions requiring special care and appropri-
ate training.

 

0

DO NOT = actions that MUST ON NO ACCOUNT be carried 
out.

This booklet cod. Doc-0083009 rev. 3 (06/2018) consists of 28 pag-
es.

Содержание 20127839

Страница 1: ...AMW P SERIES R32 06 2018 cod Doc 0083009 rev 3 EN INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS...

Страница 2: ...ting from the product s date of purchase Find the nearest Authorised Technical Support by visiting the website 9 WARNING Keep the product purchase documents for tax purposes to be presented to the Aut...

Страница 3: ...INGANDMAINTENANCE p 20 3 1 Preparation for first commissioning p 20 3 2 Putting into service p 21 3 3 Temporary shutdown p 21 3 4 Stop for an extended period of time p 21 3 5 Ordinary maintenance p 22...

Страница 4: ...ot perform any interventions upon the device on your own 9 The units contain refrigerant gas operate carefully so as to avoid damaging the gas circuit and the fin bank 9 Any gas leaks indoors can gene...

Страница 5: ...tected value to the control panel in order to control the operation of the outdoor unit and regulate the room temperature 9 Safety device replacement must be carried out by R Technical Support Service...

Страница 6: ...Cooling sound levels Superminimum sound pressure 1 20 20 22 28 30 dB A Minimum sound pressure 1 25 25 29 33 37 dB A Medium sound pressure 1 30 30 33 37 43 dB A Maximum sound pressure 1 35 35 38 41 47...

Страница 7: ...Italian Instruction s book for the installer and for the Technical Service in English user instruction booklet in Italian user instruction booklet in English Warranty Spare parts labels contact sheets...

Страница 8: ...not be disposed of in the sur rounding environment and must be kept out of children reach as it can be dangerous It must be disposed of ac cording to the regulations in force 2 6 Place of installatio...

Страница 9: ...the supplied wall plugs are suitable for the chosen support wall Avoid installing the device in hallways or passageways any obstacles or barriers that will cause the expelled air to recirculate locat...

Страница 10: ...evices are supplied with a metallic support to fix them to the wall MODEL 20 25 35 1 Fastening slots 2 Fastening holes 3 Metal support 4 Equipment overall dimensions 5 Metal support central axis 6 Equ...

Страница 11: ...as pre charged with nitrogen 1 Liquid pipe 2 Gas pipe 3 Gas connection plug 4 Pressure presence indicator 5 Fluid connection plug 1 2 3 4 5 ensure that pressure presence indicator is protruding parti...

Страница 12: ...m the prearranged connec tion on the right hand side 1 Drainage pipe 2 Condensation discharge 1 2 remove the drainage pipe on the left hand side and place it on the right hand side fit the protection...

Страница 13: ...es water 9 Avoid the entry of uncondensable gases air in the circuit otherwise with the unit in operation high pressures with the risk of damages might ensue 9 Use copper pipes for cooling systems 0 0...

Страница 14: ...ousehold appliances electric stoves etc 9 As for circuit leak and pneumatic vacuum tests refer to the matching outdoor unit instruction booklet for the installer Pipe insulation Connection pipes must...

Страница 15: ...irect it toward a suitable place for discharge insulate the joints 50 9 The discharge system must feature a suitable syphon in or der to prevent air from entering the vacuum system The sy phon also pr...

Страница 16: ...n motor C0N2 C0N3 CN11 Display SW2 1 2 3 4 ON CN1 CN36 Remote controller receiver 2 14 Electrical connection AMW P it leaves the factory completely wired and only requires a connection to the outdoor...

Страница 17: ...ing sys tem for any electrical intervention always refer to the wiring diagrams contained within this booklet take anti static precautions in case of weather conditions where humidity is less than 40...

Страница 18: ...duling and motor driven deflector settings Function keys with door open It activates and deactivates the automatic movement of the horizontal deflector or stops it in a specific position It activates...

Страница 19: ...Smart mode enabled Timer settings Timer setting value or current time display Switch on timer enabled Switch off timer enabled Motor driven deflector settings Horizontal deflector position Vertical d...

Страница 20: ...ctivated via external control if contact CN51 is closed the unit can be activated via ex ternal control OFF disabled if contact CN51 is open the unit switches off but it can be activated via external...

Страница 21: ...ouble acoustic signal is emitted the air conditioner starts in cooling mode with high ven tilation speed and active air deflector To switch off press the emergency switch again 9 This operation must b...

Страница 22: ...el wet a sponge or soft cloth with water and soap to wash once cleaning is over dry surfaces with care 9 Do not use water at a temperature that is higher than 40 C powder or abrasive detergents solven...

Страница 23: ...e system s main switch in the OFF position disconnect the cooling pipes disconnect the condensate discharge disconnect the electric connections push up and release the unit from its metallic support l...

Страница 24: ...and disposal 4 DISPOSAL Packaging materials shall be disposed of separately so as to re cover and recycle them At the end of its service life the device shall be disposed of according to the existing...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...39 0442 630111 fax 39 0442 630371 www riello it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment and accessories indicat...

Отзывы: