background image

14

INStAllAtION

A

Pipe Ø

A

mm

inches

mm

6,35

1/4

9,1

9,52

3/8

13,2

12,70

1/2

16,6

15,88

5/8

19,7

 Key

 Torque  wrench

 Flare  nut

2

3

1

Pipe Ø

tightening torque

mm

inches

Nm

6,35

1/4

18

9,52

3/8

42

12,70

1/2

55

15,88

5/8

60

A

Pipe Ø

A

mm

inches

mm

6,35

1/4

17

9,52

3/8

22

12,70

1/2

26

15,88

5/8

29

 

bring line ends with flare connection close to their cou-
pling on the unit

 

manually rotate the flare nuts by 3 - 4 turns

 

tighten the connections using a spanner and a counter 
spanner

Use a torque wrench to tighten so as to prevent damage to 
flare nuts and gas leaks.

Use equipment suitable for the system refrigerant.

Avoid using the refrigerant oil on the external part of the 
flaring.

Avoid proximity to sources of ignition in continuous op-
eration (open flames, gas household appliances, electric 
stoves, etc.).

As for circuit leak and pneumatic vacuum tests, refer to the 
matching outdoor unit instruction booklet for the installer.

Pipe insulation

Connection pipes must be thermally insulated to prevent dis-
persions of heat or formation of condensate.

 Gas  pipe

 Condensation  discharge

 Liquid  pipe

 Heat  insulation

 Adhesive  tape

5

4

4

1

2

3

 

insulate the liquid and gas pipes separately

 

use insulating material that is thicker than 15 mm

 

ensure that the insulating material adheres to the pipe 
without gaps

 

fix using adhesive tape

Do not tighten the adhesive tape too much, so as to avoid 
damaging the insulation.

Avoid partial insulation of the pipes.

In case of use with outdoor temperature above 30 °C and 
relative humidity above 80%, increase wall thickness up to 
20 mm.

For gas pipes:

 

ensure that the material used resists to temperatures up 
to 120°C

For liquid pipes:

 

ensure that the material used resists to temperatures up 

Содержание 20127839

Страница 1: ...AMW P SERIES R32 06 2018 cod Doc 0083009 rev 3 EN INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS...

Страница 2: ...ting from the product s date of purchase Find the nearest Authorised Technical Support by visiting the website 9 WARNING Keep the product purchase documents for tax purposes to be presented to the Aut...

Страница 3: ...INGANDMAINTENANCE p 20 3 1 Preparation for first commissioning p 20 3 2 Putting into service p 21 3 3 Temporary shutdown p 21 3 4 Stop for an extended period of time p 21 3 5 Ordinary maintenance p 22...

Страница 4: ...ot perform any interventions upon the device on your own 9 The units contain refrigerant gas operate carefully so as to avoid damaging the gas circuit and the fin bank 9 Any gas leaks indoors can gene...

Страница 5: ...tected value to the control panel in order to control the operation of the outdoor unit and regulate the room temperature 9 Safety device replacement must be carried out by R Technical Support Service...

Страница 6: ...Cooling sound levels Superminimum sound pressure 1 20 20 22 28 30 dB A Minimum sound pressure 1 25 25 29 33 37 dB A Medium sound pressure 1 30 30 33 37 43 dB A Maximum sound pressure 1 35 35 38 41 47...

Страница 7: ...Italian Instruction s book for the installer and for the Technical Service in English user instruction booklet in Italian user instruction booklet in English Warranty Spare parts labels contact sheets...

Страница 8: ...not be disposed of in the sur rounding environment and must be kept out of children reach as it can be dangerous It must be disposed of ac cording to the regulations in force 2 6 Place of installatio...

Страница 9: ...the supplied wall plugs are suitable for the chosen support wall Avoid installing the device in hallways or passageways any obstacles or barriers that will cause the expelled air to recirculate locat...

Страница 10: ...evices are supplied with a metallic support to fix them to the wall MODEL 20 25 35 1 Fastening slots 2 Fastening holes 3 Metal support 4 Equipment overall dimensions 5 Metal support central axis 6 Equ...

Страница 11: ...as pre charged with nitrogen 1 Liquid pipe 2 Gas pipe 3 Gas connection plug 4 Pressure presence indicator 5 Fluid connection plug 1 2 3 4 5 ensure that pressure presence indicator is protruding parti...

Страница 12: ...m the prearranged connec tion on the right hand side 1 Drainage pipe 2 Condensation discharge 1 2 remove the drainage pipe on the left hand side and place it on the right hand side fit the protection...

Страница 13: ...es water 9 Avoid the entry of uncondensable gases air in the circuit otherwise with the unit in operation high pressures with the risk of damages might ensue 9 Use copper pipes for cooling systems 0 0...

Страница 14: ...ousehold appliances electric stoves etc 9 As for circuit leak and pneumatic vacuum tests refer to the matching outdoor unit instruction booklet for the installer Pipe insulation Connection pipes must...

Страница 15: ...irect it toward a suitable place for discharge insulate the joints 50 9 The discharge system must feature a suitable syphon in or der to prevent air from entering the vacuum system The sy phon also pr...

Страница 16: ...n motor C0N2 C0N3 CN11 Display SW2 1 2 3 4 ON CN1 CN36 Remote controller receiver 2 14 Electrical connection AMW P it leaves the factory completely wired and only requires a connection to the outdoor...

Страница 17: ...ing sys tem for any electrical intervention always refer to the wiring diagrams contained within this booklet take anti static precautions in case of weather conditions where humidity is less than 40...

Страница 18: ...duling and motor driven deflector settings Function keys with door open It activates and deactivates the automatic movement of the horizontal deflector or stops it in a specific position It activates...

Страница 19: ...Smart mode enabled Timer settings Timer setting value or current time display Switch on timer enabled Switch off timer enabled Motor driven deflector settings Horizontal deflector position Vertical d...

Страница 20: ...ctivated via external control if contact CN51 is closed the unit can be activated via ex ternal control OFF disabled if contact CN51 is open the unit switches off but it can be activated via external...

Страница 21: ...ouble acoustic signal is emitted the air conditioner starts in cooling mode with high ven tilation speed and active air deflector To switch off press the emergency switch again 9 This operation must b...

Страница 22: ...el wet a sponge or soft cloth with water and soap to wash once cleaning is over dry surfaces with care 9 Do not use water at a temperature that is higher than 40 C powder or abrasive detergents solven...

Страница 23: ...e system s main switch in the OFF position disconnect the cooling pipes disconnect the condensate discharge disconnect the electric connections push up and release the unit from its metallic support l...

Страница 24: ...and disposal 4 DISPOSAL Packaging materials shall be disposed of separately so as to re cover and recycle them At the end of its service life the device shall be disposed of according to the existing...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...39 0442 630111 fax 39 0442 630371 www riello it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment and accessories indicat...

Отзывы: