15
INStAllAtION
to 70°C
2.12
Condensate discharge connection
R
AMW P
is provided with a tray that collects condensate
generated during the cooling operation, which must be con-
veyed into a suitable place for discharge. Sizes and position of
the discharge pipe are indicated below.
1
Condensate discharge pipe
1
Model
20
25
35
50
70
Connections
Condensate discharge
attachment Ø
16
mm
1
Condensate discharge pipe
2
Drainage pipe
3
Insulating material
1
2
3
—
connect a rubber drainage pipe
—
direct it toward a suitable place for discharge
—
insulate the joints
< 50
9
The discharge system must feature a suitable syphon in or-
der to prevent air from entering the vacuum system. The sy-
phon also prevents odours and insects from entering the
system.
9
The syphon must feature a plug in its lower part or must
otherwise allow for a quick disassembly for cleaning pur-
poses.
9
Ensure that all joints are properly sealed so as to prevent
water leaks.
9
The drainage pipe must be insulated for sections running
inside houses in order to prevent condensate formation on
its surface.
Drainage check:
1
Mesh filters
1
—
open the front panel
—
take out the mesh filter by grabbing the relevant fins