COMMISSIONING AND MAINtENANCE

COMMISSIONING AND MAINtENANCE

3.1

  Preparation for first commissioning

Prior to commissioning, it is necessary to check that:

 

all the safety conditions have been met

 

all distances have been respected

 

the electrical connections have been properly completed

 

power supply values are correct.

 

the earthing has been carried out correctly

 

all the connections have been properly tightened

Microswitch setting

On the main electronic board there are microswitches to man-
age some functions.

factory settings

Model

SW2

1

2

3

4

20

OFF

ON

OFF

OFF

25

OFF

ON

OFF

OFF

35

OFF

ON

ON

ON

50

OFF

ON

ON

OFF

70

OFF

ON

ON

ON

SW2_1

It selects the transmission channel between the unit and the 
remote control.
Selectable options are:
OFF = channel "A" (factory setting)
ON = channel "b"

The channel must be the same for the unit and the remote 
control.

Do not change such setting to prevent communication in-
terruptions with the remote control.

SW2_2

It enables and disables the roomcard function:
ON = enabled (factory setting).

 

if contact CN51 is open, the unit switches off and cannot be 
activated via external control

 

if contact CN51 is closed, the unit can be activated via ex-
ternal control

OFF = disabled.

 

if contact CN51 is open, the unit switches off, but it can be 
activated via external control

 

if contact CN51 is closed, the unit activates automatically

Contact CN51 is bridged by factory default.

SW2_3 e SW2_4

Do not change factory setting

Purifying filter installation

Air purifying filters to absorb microscopic dust particles, pollen, 
moulds or polluting agents are supplied with the device:

 

no. 1 antibacterial filter (green)

 

no. 1 photocatalytic filter (black)

 

no. 1 anti-formaldehyde filter (cardboard packaging)

The device is designed to be installed with two purifying 
filters. Chose among the ones supplied according to your 
needs.

For the installation:

 Mesh  filters

1

 

open the front panel

 

take out the mesh filter by grabbing the relevant fins

 Mesh  filters

 Air purifying filter

2

1

 

insert the purifying filters into the prearranged slots

 

to reposition them, proceed in reverse order

Keep the purifying filters sealed until their actual use.

Installing the purifying filters reduces the air flow and re-
sults in lower performance. It is advised to use the device at 
the highest speeds.

time setting

The current time must be set before using the remote control:

Содержание 20127839

Страница 1: ...AMW P SERIES R32 06 2018 cod Doc 0083009 rev 3 EN INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS...

Страница 2: ...ting from the product s date of purchase Find the nearest Authorised Technical Support by visiting the website 9 WARNING Keep the product purchase documents for tax purposes to be presented to the Aut...

Страница 3: ...INGANDMAINTENANCE p 20 3 1 Preparation for first commissioning p 20 3 2 Putting into service p 21 3 3 Temporary shutdown p 21 3 4 Stop for an extended period of time p 21 3 5 Ordinary maintenance p 22...

Страница 4: ...ot perform any interventions upon the device on your own 9 The units contain refrigerant gas operate carefully so as to avoid damaging the gas circuit and the fin bank 9 Any gas leaks indoors can gene...

Страница 5: ...tected value to the control panel in order to control the operation of the outdoor unit and regulate the room temperature 9 Safety device replacement must be carried out by R Technical Support Service...

Страница 6: ...Cooling sound levels Superminimum sound pressure 1 20 20 22 28 30 dB A Minimum sound pressure 1 25 25 29 33 37 dB A Medium sound pressure 1 30 30 33 37 43 dB A Maximum sound pressure 1 35 35 38 41 47...

Страница 7: ...Italian Instruction s book for the installer and for the Technical Service in English user instruction booklet in Italian user instruction booklet in English Warranty Spare parts labels contact sheets...

Страница 8: ...not be disposed of in the sur rounding environment and must be kept out of children reach as it can be dangerous It must be disposed of ac cording to the regulations in force 2 6 Place of installatio...

Страница 9: ...the supplied wall plugs are suitable for the chosen support wall Avoid installing the device in hallways or passageways any obstacles or barriers that will cause the expelled air to recirculate locat...

Страница 10: ...evices are supplied with a metallic support to fix them to the wall MODEL 20 25 35 1 Fastening slots 2 Fastening holes 3 Metal support 4 Equipment overall dimensions 5 Metal support central axis 6 Equ...

Страница 11: ...as pre charged with nitrogen 1 Liquid pipe 2 Gas pipe 3 Gas connection plug 4 Pressure presence indicator 5 Fluid connection plug 1 2 3 4 5 ensure that pressure presence indicator is protruding parti...

Страница 12: ...m the prearranged connec tion on the right hand side 1 Drainage pipe 2 Condensation discharge 1 2 remove the drainage pipe on the left hand side and place it on the right hand side fit the protection...

Страница 13: ...es water 9 Avoid the entry of uncondensable gases air in the circuit otherwise with the unit in operation high pressures with the risk of damages might ensue 9 Use copper pipes for cooling systems 0 0...

Страница 14: ...ousehold appliances electric stoves etc 9 As for circuit leak and pneumatic vacuum tests refer to the matching outdoor unit instruction booklet for the installer Pipe insulation Connection pipes must...

Страница 15: ...irect it toward a suitable place for discharge insulate the joints 50 9 The discharge system must feature a suitable syphon in or der to prevent air from entering the vacuum system The sy phon also pr...

Страница 16: ...n motor C0N2 C0N3 CN11 Display SW2 1 2 3 4 ON CN1 CN36 Remote controller receiver 2 14 Electrical connection AMW P it leaves the factory completely wired and only requires a connection to the outdoor...

Страница 17: ...ing sys tem for any electrical intervention always refer to the wiring diagrams contained within this booklet take anti static precautions in case of weather conditions where humidity is less than 40...

Страница 18: ...duling and motor driven deflector settings Function keys with door open It activates and deactivates the automatic movement of the horizontal deflector or stops it in a specific position It activates...

Страница 19: ...Smart mode enabled Timer settings Timer setting value or current time display Switch on timer enabled Switch off timer enabled Motor driven deflector settings Horizontal deflector position Vertical d...

Страница 20: ...ctivated via external control if contact CN51 is closed the unit can be activated via ex ternal control OFF disabled if contact CN51 is open the unit switches off but it can be activated via external...

Страница 21: ...ouble acoustic signal is emitted the air conditioner starts in cooling mode with high ven tilation speed and active air deflector To switch off press the emergency switch again 9 This operation must b...

Страница 22: ...el wet a sponge or soft cloth with water and soap to wash once cleaning is over dry surfaces with care 9 Do not use water at a temperature that is higher than 40 C powder or abrasive detergents solven...

Страница 23: ...e system s main switch in the OFF position disconnect the cooling pipes disconnect the condensate discharge disconnect the electric connections push up and release the unit from its metallic support l...

Страница 24: ...and disposal 4 DISPOSAL Packaging materials shall be disposed of separately so as to re cover and recycle them At the end of its service life the device shall be disposed of according to the existing...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...39 0442 630111 fax 39 0442 630371 www riello it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment and accessories indicat...

Отзывы: