- B -
SETTING MICROSWITCHES
DIP 1 MOTOR DIRECTION CHECK (ON) (POINT C)
DIP 2 TIME PROGRAMMING (ON) (POINT D)
O
PERATING MICROSWITCHES
DIP 3 Pausing time before automatic closing in normal and
pedestrian mode
(ON)
DIP 4 Jogging radio receiver
(OFF)
- automatic
(ON)
DIP 5 Single impulse command (K BUTT) jogging
(OFF)
- automatic
(ON)
DIP 6 Photocells always active
(OFF)
- Photocells active only in
closing
(ON)
DIP 7 Encoder for the PLUS model
(ON - operated)
DIP 8 Pre-blinking
(ON)
- Normal blinking
(OFF)
DIP 9 Deceleration
(ON)
DIP 10 Electronic brake
(ON-operated)
DIP 11 Gradual start
(ON- operated)
DIP 12 230V Motor
(OFF)
120V
(ON)
L
ED SIGNALS
DL1 photocells contact (NC)
DL2 stop contact (NC)
DL3 opening limit switch contact (NC)
DL4 closing limit switch contact (NC)
DL5 programming operated
DL6 gate on opening “OPEN” (green)
DL7 gate on closure “CLOSE” (red)
DL8 manual release safety device (NC)
DL9 Checking the encoder operation
T
ORQUE - ELECTRONIC TORQUE REGULATOR
The torque is regulated by rotating the Trimmer TORQUE, varying the
output voltage of motor ends,(when rotated clockwise, more torque Is
transmitted to the motor).
Such torque Is automatically Included 2 seconds after the start of every
operating cycle.
This allows the motor to have the maximum pickup when it starts.
L
OW SPEED – SPEED ADJUSTMENT DURING DECELERATION
When the DIP 9 is in ON position the speed during the deceleration is
adjusted by turning the trimmer indicated as LOW SPEED. This trimmer
is used to change the speed of the motor when the gate is approaching
the last part of the run, both in opening and closing. (to increase the
speed the trimmer must be turned clock wise).
The deceleration speed distance is set automatically by the control
panel during the “D - TIME PROGRAMMING”. The deceleration starts
automatically about 15-20 cm before the gate reaches the limit switch
in opening and closing.
E
LECTRONIC BRAKE (suggested operation)
If DIP 10 is ON, the system shall brake once the total opening or closing
have been carried out, so to avoid the inertia that would damage the
gear In the event of an Impact against the mechanical stops.
G
RADUAL START (suggested operation)
If DIP 11 is ON, a gradual movement is enabled at every operation start.
This function is not active after the encoder or another safety device
detects an obstacle.
- C -
MOTOR DIRECTION CHECK
This control is carried out to facilitate the installation of the system or
any possible future control.
1 -
After you have ensured the correct positioning of the limit
switch plates,
manually move the gate to half open position;
2 -
Put DIP 1 to the ON position
=>
The LED DL5 starts blinking
;
3 - Press the PROG button and hold it (the gate now is controlled in a
dead man mode: open, stop close stop open) =>
THE RED LED
DL7 "CLOSE" turns on and the gate starts closing
(if it does not
close, invert the wires of the motor V and W) until it reaches the limit
switch of the close position (if the gate and motor do not stop,
release the PROG button and invert the position of the J9
connector);
4 - Press the PROG button and hold it =>
THE GREEN LED DL6
"OPEN" turns on and the gate opens until it reaches the limit
switch for opening position;
5 - After 2 sec. and within 10 sec. of continuous work, both in
closing or opening, the electronic clutch intervenes
automatically. Adjust the force of the clutch by turning the
appropriate trimmer “TORQUE”.
6 - After 10 sec. of continuous work, both in opening and closing,
the automatic deceleration is activated (if DIP 9 is on ON
position) Adjust the speed of the operator requested during the
deceleration by turning the appropriate trimmer “LOW SPEED”.
7 -
At the end of the control, and of the trimmers adjustement,
position DIP1 to the OFF position.
The LED DL5 turns off,
signalling you exit from the control.
NB: The encoder and the photocells are not active during this control.
- D -
TIME PROGRAMMING
PROGRAMMING WITH ENCODER (K PLUS)
The programming can be carried out regardless of the gate position.
1 - Put DIP 2 to the ON position => the LED DL5 emits short blinkings.
2 - Push the button PROG. => the gate closes and opens automatically
2 seconds after it closed. When the opening cycle Is terminated, It
stops. Wait as long as you want the gate to remain open before the
automatin closing (excluded by DIP3 OFF).
3 - Push the button PROG. to command the gate closing (also the
pause time count before the automatic closing stops - max. 5
minutes).
4 - The gate stops as the closing limit switch plate is reached.
5 -
WHEN THE TIME PROGRAMMING IS COMPLETED, MOVE DIP
2 TO THE OFF POSITION.
If the INVERTER card is connected to the KPLUS with the KS, the card
automatically controls its slowing-down on approaching and you can
also control the operator speed (read the Instructions enclosed to the
INVERTER card).
PROGRAMMING WITHOUT ENCODER (K)
NB: DIP7 SHALL BE TO THE OFF POSITION!!
This programming is the same as that shown by the previous
paragraph.
By connecting the INVERTER card, this automatically controls its
slowing-down when approaching, and you can also determine the
speed of the operating device (read the instructions enclosed to the
INVERTER card).
NOTE:
The deceleration speed space is set automatically by the
control panel during the time programming. The deceleration
starts automatically about 15-20 cm before the gate reaches the
limit switch in opening and closing.
G
G
B
B
follows from page 30
Содержание K400 230V
Страница 8: ...I I COLLEGAMENTI ELETTRICI centralina KS cod BC07050...
Страница 18: ...F F BRANCHEMENTS LECTRIQUES coffret electronique KS cod BC07050...
Страница 29: ...G G B B ELECTRIC CONNECTIONS electric board KS code BC07050...
Страница 40: ...D D ELEKTROANSCHL SSE elektronische steuerung KS code BC07050...
Страница 51: ...E E S S CONEXIONES EL CTRICAS panel electronico KS c d BC07052...